NO8

normally open contact digital output 8

NC8

normally closed contact digital output 8

The maximum length of the connecting cables of the digital outputs is 100 m (328 ft).

The maximum current allowed on the loads is 10 A.

ANALOG OUTPUTS

Analog outputs 1, 2 and 3.

Terminal

Meaning

VDC

power supply driving analog output 1 (24 VDC, 50 mA max.)

AO1

analog output 1 (PWM signal)

GND

ground

AO2

analog output 2 (configurable via configuration parameter for 0-20 mA / 4-20 mA / 0-10 V signal)

AO3

analog output 3 (configurable via configuration parameter for 0-20 mA / 4-20 mA / 0-10 V signal)

The maximum length of the connecting cables of the PWM analog output is 1 m (3.280 ft); the one of the connecting cables of

the 0-20 mA / 4-20 mA / 0-10 V analog outputs is instead of 30 m (98 ft).

For the settings about the analog outputs look at chapter 6 “CONFIGURATION”.

The analog output 1 is usable on condition that the controller is powered in alternate current and the phase powering the controller is the

same powering the user driven by the output.

DIGITAL INPUTS

Digital inputs 1, 2, 3, 4, 5, 6 and 7.

Terminal

Meaning

DI1

digital input 1

DI2

digital input 2

DI3

digital input 3

DI4

digital input 4

DI5

digital input 5

DI6

digital input 6

DI7

digital input 7

COM

common digital inputs