EVCO EPH4EXP Hardware manual User Manual

Page 108

Advertising
background image

EVCO S.p.A.

c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324

page 108 of 116

3 non optoisolated inputs,

configurable

via

configuration parameter for

PTC / NTC / Pt 1000 probes

/ 0-20 mA / 4-20 mA / 0-5 V

ratiometric

/

0-10

V

transducers.

5 non optoisolated inputs,

configurable

via

configuration parameter for

PTC / NTC / Pt 1000 probes

/ 0-20 mA / 4-20 mA / 0-5 V

ratiometric

/

0-10

V

transducers.

3 non optoisolated inputs,

configurable

via

configuration parameter for

PTC / NTC / Pt 1000 probes

/ 0-20 mA / 4-20 mA / 0-5 V

ratiometric

/

0-10

V

transducers.

c-pro 3 hecto+

c-pro 3 mega+

c-pro 3 EXP hecto+

4 non optoisolated inputs, of

which 3 configurable via

configuration parameter for

PTC / NTC / Pt 1000 probes

/ 0-20 mA / 4-20 mA / 0-5 V

ratiometric

/

0-10

V

transducers and 1 for NTC

probes.

8 non optoisolated inputs, of

which 5 configurable via

configuration parameter for

PTC / NTC / NTC 2 / NTC 3

/ Pt 1000 probes / 0-20 mA /

4-20 mA / 0-5 V ratiometric /

0-10 V transducers and 3

configurable

via

configuration parameter for

NTC / 0-20 mA / 4-20 mA.

4 non optoisolated inputs, of

which 3 configurable via

configuration parameter for

PTC / NTC / Pt 1000 probes

/ 0-20 mA / 4-20 mA / 0-5 V

ratiometric

/

0-10

V

transducers and 1 for NTC

probes

Power supply 0-5 V ratiometric transducers: 5 VDC (+0% -12%), 40 mA max.

Power supply 0-20 mA / 4-20 mA / 0-10 V transducers: 24 VDC (+50% -25%), 120 mA max.

The devices incorporate a restorable thermal protection of the power supplies against the

short circuit and the overload.

PTC analog inputs (990

@ 25 °C, 77 °F)

Kind of sensor:

KTY 81-121.

Working range:

from -50 to 150 °C (-58 to 302 °F).

Accuracy:

±0.5% of the full scale between -40 and 100 °C, ±1 °C

between -50 and -40 °C and between 100 and 150 ° C.

Resolution:

0.1 °C.

Conversion time:

100 ms.

Protection:

no protection.

NTC analog inputs (10K

@ 25 °C, 77 °F)

Kind of sensor:

β

3435.

Working range:

from -50 to 120 °C (-58 to 248 °F).

Accuracy:

±1 °C.

Resolution:

0.1 °C.

Conversion time:

100 ms.

Protection:

no protection.