Smart/vigil concentrators programming, Programming inputs/outputs – Interlogix Monitor XL Hardware Guide User Manual

Page 33

Advertising
background image

22-0375 rev1.1

Monitor ISM/xL™ Hardware Guide

29

Press

Save

. The next address is the third Smart/Vigil module address. Enter the next consecutive address

number after the last. E.g. “15283”.

Program the same as the last 2 addresses but only enter “4” for 16 outputs. “0” for inputs.

This will now supply 64 inputs and 80 outputs. For smaller Chubb Smart/Vigil systems, it is only necessary to
program the number of inputs/outputs required. All 3 addresses may not be needed and other module addresses
could occupy their places.

Exit the module programming and then go back to module programming and the first Smart/Vigil module address.
This initializes the module.

Press

Save

. The following screen supplies three programming options. HSC (NOT USED), PRN (printer),

SMR

(Chubb Smart/Vigil Concentrators).

Printer programming is the same as with a Printer module (discussed later in this manual).

Please refer to

programming it with that module, to program it with the Smart module.

Press the button below SMR.

Smart/Vigil Concentrators Programming

The next screen displays programming for the first Smart/Vigil concentrator.

The top line displays: Conc1 (concentrator 1), [enable conc1, with the cursor under this box (press LCD
keypad left or right arrow keys) press any key number to make the box a to enable the conc.] T [is it
necessary to test a seismic connected to this concentrator (seismic concentrator, safe/vault concentrator), enter
if yes], S

[how many seismics require a test signal (seismic concentrator has 1 seismic, a safe/vault

concentrator can have 1 seismic configured as a safe or a maximum of 5 for a vault) make each box a for each
seismic]. E.g. for a commercial concentrator there are no seismics. Only enable the conc. and do not enable any
test selections. Press Save.

Programming for the next conc. is displayed. Programming for all concentrators continue in the same way.

Programming Inputs/Outputs

Programming inputs is the same as any inputs with e.g. Expander module.

With the Smart/Vigil module occupying the first module location, inputs for it begin at 009. 001 – 008 being on the
ISM/AFx main panel.

When programming outputs, they begin at 009. 001 – 004 (005 – 008 not existing) being on the ISM/AFx main
panel.

It is very IMPORTANT to remember that the 9

th

output for any concentrator with seismics to test must be

programmed as “AREA ON” [bCAPL programmable output code: 01.10XX (XX = area #01 – 10)] to generate the
test.

Use the following chart to compare Chubb Smart/Vigil inputs/outputs as they are converted to ISM/AFx.