Adding Any Power Supply to the Module Bus

An additional power supply’s positive is not connected to the main control module bus positive with an isolating
diode, as was previously done.

The modules using power from the additional power supply have their module bus Data A and B interconnected as
normal.

The additional power supply’s negative is connected common to the module bus negative.

The additional power supply’s positive is never connected to the module bus positive.

Communication Connections between the Main Controller and the Director PC
Software

Direct Connect to PC

Main
Panel
Mother
board

14

3
2

5

14

3
2

CTS/RTS
RTS/CTS
DSR/DTR

DTR/DSR

RI/RI

CD/CD

TB1

4

TB1

5

green

black

13

2

TB

1

6

0V
B
A

white

RS485

RX/RX

TX/TX

GND/GND

RS485 Communication Cable

Cable shield (do not ground at the PC)

To additional panels (maximum 30)

0V B A

Cable
Shield:
Connect to
the chassis/
earth
ground at
one panel
only (e.g.
1st or last)

black

white

green

NOTE: The
A and B
connections
here are
reversed
relative to
the panel(s).

P/N 120-3401 (24 AWG, 4wires, shielded)

14

3
2

Currently
Supplied
Version
RS485
Converter
P/N
650-9061

DB9 (insert into
free serial port on
the specific PC)

NOTE:
The A and B
connections
are one to one.

DB9 (insert into
free serial port on
the specific PC)

Previous Version
RS485 Converter
P/N 11-0343

(+)12V

(

-

)0V

Data B
Data A

black

green

white

green

black

white

A

B

GND

+12V

GND

Additional power may be needed when
connecting multiple panels. Connect 12VDC
and parallel neg0Vgnd at either converter’s
terminal block.

Modem Connection for PC Communications

Main
Panel
Mother
board

14

3
2

5

14

3
2

CTS/RTS
RTS/CTS
DSR/DTR

DTR/DSR

RI/RI
CD/CD

TB

1

4

TB

1

5

green

black

13

2

TB

1

6

0V
B
A

white

RS485

RX/RX

TX/TX

GND/GND

RS485 Communication Cable

Cable shield (do not ground at the modem)

To additional panels (maximum 30)

0V B A

Cable

Shield:
Connect to
the chassis/
earth

ground at

one panel

only (e.g.

1st or last)

black
white

green

NOTE: The

A and B
connections

here are
reversed
relative to
the panel(s).

P/N 120-3401 (24 AWG, 4wires, shielded)

14

3
2

Currently
Supplied
Version
RS485
Converter
P/N
650-9061

NOTE:

The A and B
connections

are one to one.

Previous Version

RS485 Converter

P/N 11-0343

(+)12V

(

-

)0V

Data B
Data A

black

green

white

green

black

white

A

B

GND

+12V

GND

Connect via DB9-
DB25 and a null-
modem adapter
(or equiv.cable)

MODEM

Connect via DB9-DB25 and a null-modem adapter (or equiv.cable)

Additional power may be needed when
connecting multiple panels. Connect 12VDC
and parallel neg0Vgnd at either converter’s
terminal block.