Smart/vigil module test and diagnostics, Printer option (smart module only), Smart/vigil concentrator tests – Interlogix Monitor XL Hardware Guide User Manual

Page 35

Advertising
background image

22-0375 rev1.1

Monitor ISM/xL™ Hardware Guide

31

When selecting SMR, the status of each concentrator will display and pressing the LCD keypad left or right arrow
keys will display each concentrator’s status. Pressing Next will return to the main Smart/Vigil module menu.

The concentrator may state that it’s OK. Tmpr = conc. tamper. Tmpr Au_ERR = the concentrator is in tamper
and has had an authentication error (concentrator substitution e.g. conc. dis/reconnected). PTmpr = the
Smart/Vigil module itself is in tamper and the concentrator is OK.

Smart/Vigil Module Test and Diagnostics

Using Service user ID/PIN, enter the Test menu and select App. Select SMA for Smart/Vigil module.

HSC

is NOT USED.

Printer Option (Smart Module ONLY)

Pressing PRN will allow you to control and do tests on the printer.

Pressing Ctrl will give you the options to Strt: start the printer, Cncl: cancel pending messages, Plg: print

the entire log.

Pressing L/B will do a printer port loop back test the same as the HSC loop back test on the HSC/Printer

module (discussed later in this manual) to test printer hardware integrity.

Smart/Vigil Concentrator Tests

Pressing SMR from the SMA menu will display Alog for point analog. Pressing it will display the condition of a

Smart/Vigil input using different values. The Smart/Vigil input point numbers can be scrolled using the LCD
keypad left or right arrow keys. Values indicate: “018” = normal, “001” = tamper, “032” = in alarm. These readings
may vary but still be within these ranges.

Pressing Vault Tst will test all seismics connected to any concentrators through out the system. The display will

change to “Testing Vault Concentrators” and stay on for 1 second. The test occurs in 15 to 20 seconds
afterwards.

After this delay is finished, go to the Analog screen again. Scroll the various points until the ones that may have
had a test fail display. They will display with an “F” (failed).

Pressing TFAL (test fail) will display the concentrator number and seismic that failed. E.g. Conc: 001

(concentrator #1), F-X-F-X-X (seismics 2 and 3 failed the test).