22-0375 rev1.1

Monitor ISM/xL™ Hardware Guide

55

LEDs

AC Mains On

(green) – on with electrical present.

Power ON

(green) – on if Auxiliary DC power is present

Trouble

(yellow) Normal = not on. – will flash on and off for:

AC Mains failure.

Battery loss.

Module Bus (SNAPP) not active.

– turns on solid if one or more of the board tampers are active.

Processor OK
– normally will flash on and off slowly.
– will flash on and off rapidly when VBUS is present.

Relay Trouble Output

– will change state with any trouble mentioned above present.

Power Supply Selection Jumpers P4 to P10

Jumpers

Power Supply Type

and other selections

P4 P5 P6 P7 P8

Module Bus(SNAPP) and VBUS Master

(P9 and P10 are ignored)

IN IN

VBUS Slave

(set P9 and P10 Slave Address)

IN OUT

Module Bus (SNAPP) ONLY

OUT

IN

Stand Alone, no Module Bus or VBUS

OUT

OUT

110V Operation

IN

220V Operation

OUT

Relay Test –

disconnect the module bus (SNAPP). Momentarily insert P7

jumper and remove again. Relay will cycle on, off for 10 secs.

OUT

Defeat Battery –

where a standby battery is not required, insert P8 jumper

and the system will ignore battery monitoring. IMPORTANT: This jumper must
be left OUT for battery monitoring.

OUT















Modu

le Bu

s

(SNAP

P

)

VBUS

VBUS

Main

Control

Unit

MASTER – P4, P5 in
SLAVE – P4 in, P5 out
SNAPP only – P4 off, P5 in
Stand Alone – P4, P5 out

Master Unit communicating
to the main control unit on
the Module Bus. The Module
Serial # on its sticker is
programmed into the Module
Program Section.
– P4 & P5 in
– P9, P10 ignored

Slave unit # 1 on Master
Unit’s VBUS. The Module
Serial # on its sticker is
ignored.
– P4 in, P5 out.
– P9, P10 out = Address 0
or Slave #1

Slave unit # 2 on Master
Unit’s VBUS. The Module
Serial # on its sticker is
ignored.
– P4 in, P5 out.
– P9 out, P10 in = Address
1 or Slave #2

Parallel
Connections.

Module Power Supply

0V and VBUS.
A 12VDC
connection is
not needed.

VBUS

VB

U

S

S

N

APP

Module Power Supply

Module Power Supply

VBUS

NOTE: VBUS is an internal communication bus that related VBUS modules
are used with. The VBUS is not intended for external use. It has been
designed to be used in a protected enclosure with adjoining interconnection
between modules in the same enclosure. It communicates with the main
control over the Module Bus (SNAPP) which is for external communications.

Jumpers

Power Supply

Slave Address

P9 P10

1 OUT

OUT

2 OUT

IN

3 IN

OUT

4 IN

IN