Page 108

Code Description

L or

H

Procedure

108

Flame lost in run

L

1. Check main valve wiring and operation -

correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame

detector, flame detector siting or flame rod

position.
5. If steps 1 through 4 are correct and the fault

persists, replace the module.

109

Ignition failed

L

1. Check main valve wiring and operation -

correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat turndown tests.
4. Check ignition transformer electrode, flame

detector, flame detector siting or flame rod

position.
5. If steps 1 through 4 are correct and the fault

persists, replace the module.

110

Ignition failure occurred

H

Hold time of recycle and hold option. Will not be

a lockout fault. Hold Only. Internal hardware test.

Not a lockout.

111

Flame current lower than weak

threshold

H

Hold time of recycle and hold option. Will not be

a lockout fault. Hold Only. Internal hardware test.

Not a lockout.

113

Flame circuit timeout

L

Flame sensed during Initiate or off cycle, hold 240

seconds, if present after 240 seconds, system will

lockout.

119

Control Interaction Fault

H

Flap valve identifications configured incorrectly.

122

Lightoff rate proving failed

L

1. Check wiring and correct any potential wiring

errors.
2. Check VFD’s (Variable-speed Fan Drive)

ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.

123

Purge rate proving failed

L

1. Check wiring and correct any potential wiring

errors.
2. Check VFD’s (Variable-speed Fan Drive)

ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.

128

Fan speed failed during prepurge

H or

L

1. Check wiring and correct any potential wiring

errors.
2. Check the VFDs (Variable-speed Fan Drive)

ability to change speeds.
3. Change the VFD
4. If the fault persists, replace the module.