NeoTherm Boilers and Water Heaters

Page 63

Fig. 73 – Flap Valve Configuration Screen

Notice that there are two items on this screen.
Controller ID -

This is the ID number of the flap valve

associated with this controller. (We will set

the ID number for the other controller in this

boiler in a moment.)

Number of controllers -

This is the total number of controllers

in the whole system. (For example, in a

system with four boilers, there will be eight

controllers.) See Table 14.

You need to set both of these values on the Flap

Valve Configuration screen for each controller

in the system.

table 14 – number of Controls

Number of

boilers

Number of

controls

2

4

3

6

4

8

For example, if your system has three boilers,

there would be a total of six controllers (two

for each boiler), so you would enter “6” for

Number of Controls.

5. Because you are changing a parameter that

is related to safety, the system will present a

warning that looks like this:

fig. 74 – Parameter Safety Warning

Press OK to continue. The system will ask you

to login before you make a change.

Note that any changes you make will apply

only to one controller – the controller you have

already selected. If you want the same change

to apply to other controllers, you must change

each of them separately.

Once you change one of these safety-related

parameters, you must finish the verification

process, or the control system will not let the
boiler operate

. Each control in a boiler must

be verified separately.

6. Press again on the line for Controller ID. Table

15 shows how the Primary and Secondary

controls should be numbered for each of the

boilers.

Boiler 1

Boiler 2

Boiler 3

Boiler 4

Primary control

1

3

5

7

Secondary control

2

4

6

8

table 15 – flap Valve Controller ID addressing