NeoTherm Boilers and Water Heaters

Page 69

8. Press the left-arrow or right-arrow until you see

the Central Heat screen (Fig. 87).

fig. 87 – Central Heat

Setpoint source -

This sets the source of the System sensor

input used to control the system. The

options here are Local and 4-20 mA.

(For instructions on setting up for a 4-20

mA input, see Job #5 in the section on

“Installation Options.”)

Setpoint -

This is the same as the LL CH Setpoint on

the Lead/Lag Master Configuration screen

(Fig. 85).

Time of day setpoint -

This is the same as the LL CH Time-Of-

Day Setpoint on the Lead/Lag Master

Configuration screen (Fig. 85). (See the

material on “About the ‘Time of Day’

Function at the end of this section)

4 mA water temperature -

If a 4 – 20 mA input is used to adjust the

setpoint, this entry sets the low limit of the

control range. (In the example shown here,

an input of 4 mA would result in a setpoint of

90°F.)

20 mA water temperature -

If a 4 – 20 mA input is used to adjust the

setpoint, this entry sets the high limit of the

control range. (In the example shown here,

an input of 20 mA would result in a setpoint

of 120°F.)

9. Press the left-arrow or right-arrow until you see

the Domestic Hot Water screen (Fig. 88).

fig. 88 – Domestic Hot Water

The arrangement for Domestic Hot Water can

be set up in several ways. For details, see the

section on “Lead/Lag Domestic Hot Water.”

DHW Setpoint -

This is the same as the DHW Setpoint on the

Lead/Lag Master Configuration screen.

DHW Time of day setpoint -

This is the same as the DHW Time-Of-

Day Setpoint on the Lead/Lag Master

Configuration screen. (See the material on

“About the ‘Time of Day’ Function at the end

of this section.)

DHW Priority method -

This determines the way the system gives

priority to the DHW demand (if DHW is

given priority on the bottom line of the

screen.)

DHW priority override time -

If Domestic Hot Water has priority (see

the next line below), this sets how long the

DHW loop will have priority before returning

to control by the Lead/Lag Central Heat

setpoint.

DHW has priority over CH? -

Choose Central Heating priority or Domestic

Hot Water priority.