LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual
Page 88

LAARS Heating Systems
Page 84
2. If the system was running, the following
screen would normally show the current
activity of each unit in the multiple boiler
arrangement. See Fig. 118.
fig. 118 – lead/lag Screen
3. Press the button for Lead Lag Master. Fig.
119 shows the screen that follows.
fig. 119 – lead/lag master Screen
4. Press the Configure button. The display will
present the Lead/Lag Master Configuration
Screen (Fig. 120).
Fig. 120 – Lead/Lag Master Configuration
Set the DHW setpoint on this screen.
5. Press the button for Advanced Settings. This
leads to a “ring” of related screens, and you can
scroll through the list by pressing one of the
left- or right-arrow symbols. Press the left-
arrow or right-arrow until you see the Domestic
Hot Water screen (Fig. 121).
fig. 121 – Domestic Hot Water
Set the last line to give priority to the DHW
function.