LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 92

Advertising
background image

LAARS Heating Systems

Page 88

Label

Description

How to Reach

DHW

(Domestic

Hot Water)

pump control

The DHW pump (Pump C) can be turned

on manually, or it can be set to operate

automatically. If it is turned on then it remains

on until changed back to Auto. In Auto mode

it operates according to the DHW demand, the

start delay timer and the overrun time.

Home screen/ Select controller/ Status

Summary screen/ Configuration/ Pump

Configuration/ Left- or Right- arrow

buttons/ DHW Pump screen/ Control

Settings button

DHW

(Domestic

Hot Water)

pump cycle

count

This can be written to a new value if the pump

or controller is replaced.

Home screen/ Select controller/ Status

Summary screen/ Configure button/

Configuration List/ Select Statistics

Configuration line

DHW

(Domestic

Hot Water)

Setpoint

This setpoint is used for Domestic Hot Water

whenever the Time-Of-Day switch is off or not

connected (unused).

If Lead/Lag enabled –

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen

DHW

(Domestic

Hot Water)

TOD (Time

of Day)

Setpoint

This setpoint is used for Domestic Hot Water

when the Time-Of-Day switch is on.

If Lead/Lag enabled –

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen

Flap valve

controller ID

Each flap valve has a unique ID number. On

a system with 4 boilers, there would be 8 flap

valves, numbered 1 through 8.

Home screen/ Select controller/ Status

Summary screen/ Configuration/ Flap

Valve Configuration

Lead lag CH

outdoor reset

enable

This line is used to turn on the Outdoor Reset

function when the Lead/Lag system is enabled.

If Lead/Lag enabled –

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen/ Advanced Settings

button/ Left- or Right- arrow buttons/

Outdoor Reset screen

Lead lag CH

setpoint

This is the setpoint used for Central Heat when

the Lead/Lag system is enabled.

If Lead/Lag enabled –

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen

Lead lag

CH setpoint

source

When Lead/Lag is enabled, this sets the source

of the System sensor input used to control the

system. The options here are Local and 4-20

mA.

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen/ Advanced Settings

button/ Left- or Right- arrow buttons/

Central Heat screen

Lead lag CH

TOD setpoint

This is a different setpoint used for Central Heat

when the Lead/Lag system is enabled and the

input from the Time Of Day switch is “true.”

If Lead/Lag enabled –

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen