4 installation jobs, Job a – note for systems using common venting, Job b - naming the controllers – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 60

Advertising
background image

LAARS Heating Systems

Page 56

9.4

Installation Jobs

note – To install your system, you will not need to do

all of the installation jobs listed here. Please refer

to Section 9.3 for a list of specific installation jobs

necessary to install your system.

Job a – note for Systems Using Common

Venting

If multiple NeoTherm units share a single vent, the

system must be engineered by a competent venting

specialist. The design involves the selection of

draft-inducing equipment, hardware and controls

to properly balance flue gas pressures. Do not

common vent NeoTherm units unless the vent system

meets this requirement. NeoTherm units are never

permitted to share a vent with Category I appliances.

Job B - naming the Controllers

(This is an individual function – do this for each of the controls.
Use the separate Operator Interface on each boiler.)

Each boiler includes two separate controls, as shown

in Fig. 49. In a system with four boilers, there will be

eight separate controls. See Fig. 50. The first job is

to name each of these controllers.

1. We will start by entering a name for the first

controller in the line – the Primary controller on

Boiler 1. Start at the “Home” screen. Press the

icon for the Primary control.

fig. 53 – Home Screen

2. The system will present the Status Summary

screen for that controller. See Fig. 54.

fig. 54 – Status Summary Screen

3. Select the “Configure” button in the bottom

left-hand corner of the display. Figure 55

shows the Configuration menu.

Fig. 55 – Configuration Menu

4. Select the line for System Identification and

Access.

Advertising
This manual is related to the following products: