LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 82

Advertising
background image

LAARS Heating Systems

Page 78

control to Manual, this forces the burner to run

at full combustion so you can adjust the gas

valve for the correct CO

2

output.

Figure 100 shows the adjusting points on the

gas valve. Adjust the High Fire screw to get

the proper CO

2

level for high fire. See Table

17. To raise the high fire CO

2

level, turn the

High Fire adjustment screw counter-clockwise.

To lower the high fire CO

2

level, turn the screw

clockwise.

(Make the adjustment in small steps of 1/8 turn

to avoid “overshooting” the correct setting.

The valve is built with a bit of “backlash.”

This makes it appear that changing the

adjustment does not change the CO

2

level

when you first stop turning the control in one

direction, and start turning it the other way.

Once the backlash has been taken up, the

control will be quite sensitive.)

13. Repeat steps 10 through 12, except this time

set the fan speed RPM to 1200rpm. (Again, the

actual RPM will not go this low – the control

will limit the fan speed to the minimum set

at the factory.) This will force the boiler to

operate in low fire. Adjust the Low Fire screw

so the CO

2

is 0.5% lower than the high fire

CO

2

. To raise the low fire CO

2

, turn the Low

Fire adjustment screw clockwise. To lower the

low fire CO

2

, turn the screw counter-clockwise.

14. The adjustment you made for the Low Fire

setting could affect the High Fire setting, so

you need to re-check the High Fire setting. Go

back to the Operations screen and set the Firing

Rate back to 6500 RPM. The CO

2

should

still be about at the level listed in Table 17. If

the CO

2

is not correct, repeat the steps listed

above.

15. Set the Firing Rate back to 1200 RPM, and re-

check the CO

2

during Low Fire.

16. Once the CO

2

values are correct for both High

Fire and Low Fire, go back to the Operation

screen and select Automatic operation. At this

point, you have set up the Primary burner for

this boiler.

17. Now you can do the same setup for the

Secondary burner on this boiler. To do this,

you need to shut off the Primary burner. On

the Secondary control, you set the High and

Low Fire RPM and check the CO

2

output for

each condition. We will review the process

quickly here:

• On the Home screen, press the icon for the

Secondary controller.

• On the Status Summary screen, press the

Operation button.

• On the Operation screen, press the Login

button and login using the installer-level

password, then press OK.

• Now you can change the Firing Rate RPM for

the Secondary burner. Enter 6500 RPM for the

High Fire value. On the left side of the screen,

in the space for Normal Setpoint, select Manual

and press OK. Adjust the High Fire screw to

get the CO

2

level listed in Table 17.

• Set the fan speed RPM to 1200rpm. Adjust

the Low Fire screw so the CO

2

level reaches the

CO

2

level listed in Table 17.

• Re-check the High Fire setting at 6500 RPM.

The CO

2

should still be about 8.5%.

• Re-check the CO

2

during Low Fire at 1200

RPM.

• Once the CO

2

values are correct for both High

Fire and Low Fire, go back to the Operation

screen and select Automatic operation. At this

point, you have set up the Secondary burner for

this boiler.

• Go back to the Home screen and press the

icon for the Primary control. On the Status

Summary screen, press the Operation button.

On the Operation screen, press the Burner

button to turn on the Primary burner.

18. Once both burners are set up properly, operate

both burners together as described below, and

check the CO

2

levels with the unit operating at

high fire and at low fire. The final CO

2

values

at high fire should be as listed in Table 17

±0.2%. At low fire, the CO

2

should be about

0.5% lower than the high fire CO

2

reading. (The

offset is more important than the actual CO

2

value)

Monitor the CO

2

and CO levels for one

complete operating cycle. The CO should

never be more than 150 ppm. The CO

2

level

should also track between the high and low

limits listed in the table.

Setting the fan speed RPMs for both burners

operating together -

• It is important that both burners operate at

the same fan speed. Before changing the fan

speeds, turn off the call for heat.

• Set the fan speed for each burner separately,

using the procedure we described earlier - steps

6 though 10 for the Primary burner, and step 17

for the Secondary burner. On each burner, enter

a value of 6500 RPM for the high fire test.

• Once you have set both burners to run at

6500 RPM, turn on the call for heat, and check

the results as described above.

Advertising
This manual is related to the following products: