5 pump requirements, 1 boiler flow and head requirements, 2 water heater flow and head requirements – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual
Page 21: Neotherm boilers and water heaters
Advertising

NeoTherm Boilers and Water Heaters
Page 17
Section 5
PUmP reQUIrementS
5.1
neotherm Boiler flow and Head requirements
5.2
neotherm Water Heater flow and Head requirements
table 7 - Water flow requirements
table 8 - neotherm Water Heater flow Data
Temperature Rise in °F
20°F
25°F
30°F
35°F
40°F
45°F
Flow
GPM
H/L-Ft
Flow
GPM
H/L-Ft
Flow
GPM
H/L-Ft
Flow
GPM
H/L-
Ft
Flow
GPM
H/L-Ft
Flow
GPM
H/L-Ft
95
30
75
20
62
15
54
11
48
9
42
7
Temperature Rise in °c
11.0°c
13.7°c
16.5°c
19.3°c
22.0°c
24.7°c
Flow
LPm
H/L-m
Flow
LPm
H/L-m
Flow
LPm
H/L-m
Flow
LPm
H/L-m
Flow
LPm
H/L-m
Flow
LPm
H/L-m
359
9.0
283
6.0
234
4.5
204
3.3
182
2.7
159
2.1
Temperature Rise
20°F
11.0°c
Flow GPM
H/L-Ft
Flow LPm
H/L-m
95
30
359
9.0
Notes -
Figures listed are for soft/normal water.
Maximum hardness of 10 grains per gallon allowed.