NeoTherm Boilers and Water Heaters

Page 17

Section 5

PUmP reQUIrementS

5.1

neotherm Boiler flow and Head requirements

5.2

neotherm Water Heater flow and Head requirements

table 7 - Water flow requirements

table 8 - neotherm Water Heater flow Data

Temperature Rise in °F

20°F

25°F

30°F

35°F

40°F

45°F

Flow

GPM

H/L-Ft

Flow

GPM

H/L-Ft

Flow

GPM

H/L-Ft

Flow

GPM

H/L-

Ft

Flow

GPM

H/L-Ft

Flow

GPM

H/L-Ft

95

30

75

20

62

15

54

11

48

9

42

7

Temperature Rise in °c

11.0°c

13.7°c

16.5°c

19.3°c

22.0°c

24.7°c

Flow

LPm

H/L-m

Flow

LPm

H/L-m

Flow

LPm

H/L-m

Flow

LPm

H/L-m

Flow

LPm

H/L-m

Flow

LPm

H/L-m

359

9.0

283

6.0

234

4.5

204

3.3

182

2.7

159

2.1

Temperature Rise

20°F

11.0°c

Flow GPM

H/L-Ft

Flow LPm

H/L-m

95

30

359

9.0

Notes -

Figures listed are for soft/normal water.

Maximum hardness of 10 grains per gallon allowed.