NeoTherm Boilers and Water Heaters

Page 15

Section 4

GaS SUPPly anD PIPInG

4.1

Gas Supply and Piping

Gas piping should be supported by suitable hangers

or floor stands, not the appliance.
Installers should refer to local building and safety

codes or, in the absence of such requirements, follow

the National Fuel Gas Code, ANSI Z223.1 NFPA 54

and/or CSA B149.1, Installation Codes.
Review the following instructions before proceeding

with the installation.
1. Verify that the appliance is fitted for the proper

type of gas by checking the rating plate.

NeoTherm will function properly without the

use of high altitude modification at elevations

up to 10,000 feet (3050 m).

2. The maximum inlet gas pressure must not

exceed 13” W.C. (3.2 kPa). The minimum inlet

gas pressure is 4” W.C. (1.0 kPa).

3. Refer to Tables 6A, 6B, 6C and 6D to size the

piping.

4. Run the gas supply line in accordance with all

applicable codes.

5. Locate and install manual shutoff valves in

accordance with state and local requirements.

6. A sediment trap must be provided upstream of

the gas controls.

7. All threaded joints should be coated with

piping compound resistant to the action of

liquefied petroleum gas.

8. The appliance and its individual shutoff valve

must be disconnected from the gas supply

piping during any pressure testing of that

system at test pressures in excess of 1/2 PSIG

(3.45 kPa).

9. The unit must be isolated from the gas supply

system by closing its individual manual shutoff

valve during any pressure testing of the gas

supply piping system at test pressures equal to

or less than 1/2 PSIG (3.45 kPa).

10. The appliance and its gas connection must be

leak tested before placing it in operation.

11. Purge all air from gas lines.

WarnInG

Open flame can cause gas to ignite and result in

property damage, severe injury, or loss of life.

note - The NeoTherm appliance and all other gas

appliances sharing the gas supply line must be firing

at maximum capacity to properly measure the inlet

supply pressure. The pressure can be measured

at the supply pressure port on the gas valve. Low

gas pressure could be an indication of an under-

sized gas meter, undersized gas supply lines and/

or an obstructed gas supply line. Some NeoTherm

units are equipped with low and high gas pressure

switches that are integrally vent limited. These types

of devices do not require venting to atmosphere.