7 electrical connections, 1 main power, 2 pump connections – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 32

Advertising
background image

LAARS Heating Systems

Page 28

Section 7

eleCtrICal ConneCtIonS

WarnInG

The appliance must be electrically grounded in

accordance with the requirements of the authority

having jurisdiction or, in the absence of such

requirements, with the latest edition of the National

Electrical Code, ANSI/NFPA 70, in the U.S. and

with latest edition of CSA C22.1 Canadian Electrical

Code, Part 1, in Canada. Do not rely on the gas

or water piping to ground the metal parts of the

boiler. Plastic pipe or dielectric unions may isolate

the boiler electrically. Service and maintenance

personnel who work on or around the boiler, may

be standing on wet floors and could be electrocuted

by an ungrounded boiler. Electrocution can result in

severe injury or death.

Single pole switches, including those included in

safety controls and protective devices, must not be

wired in a grounded line.
All electrical connections are made on the terminal

blocks that are located inside the control panel.

note - All internal electrical components have been

prewired. No attempt should be made to connect

electrical wires to any other locations except the

terminal blocks.

The wiring connections are shown in Figures 19 and 21

.

note - Do not make and break the line voltage to the

NeoTherm unit as a signal to call for heat.

On a system operating as a Lead/Lag installation -

A “call for heat/ end call for heat” must be connected

to the Primary TT or Interlock terminals (terminals 5

and 6 on TB7) on the controller which is acting as the

Lead/Lag master.
On a boiler operating individually -

A “call for heat/ end call for heat” must be connected

to the Primary Thermostat terminals (terminals 5

and 6 on TB7). Any jumper to the System terminals

(terminals 3 and 4 on TB6) must be removed. For

details, see Section 9.

Some NeoTherm components are designed to have

constant voltage during normal operation. If the

NeoTherm’s supply voltage is toggled as a call for

heat signal, premature failure of these components

may result.
The NeoTherm unit does not recognize 4 mA as a

signal to shut off. If the call for heat is not connected

between the field interlock terminals, NeoTherm will

remain in low fire when it sees 4 mA as a modulating

signal.

Caution

The supply voltage to the NeoTherm must not

be disengaged, except for service or isolation, or

unless otherwise instructed by procedures outlined

in this manual. To signal a call for heat, use the

correct terminals as instructed in Section 9.

7.1

main Power

Connect a 15 A fused, 120 VAC supply to the main

power switch. The hot leg is connected directly to

the switch. The neutral leg is connected directly to

the white wire. The ground wire can be connected to

the grounding wire in the junction box. (See Figure

27.)

7.2

Pump Connections

The NeoTherm energizes the appropriate pump

contacts when it receives a call for heat or domestic

hot water. Once the call for heat or DHW is satisfied,

the pump will remain on for the defined pump

overrun time.

note - The contacts for the System and DHW

pumps are dry contacts. Appropriate voltage must be

supplied to the System and DHW pumps for proper

operation. The Boiler pump contact (max 7.4 FLA) is

fed by 120 V internally from the main power feed.

Due to the size of the pumps required to operate

the boiler and system properly, it is likely that the

maximum ratings of the Boiler pump contacts will

be exceeded (120 Volts, 7.4 FLA). In this case, an

additional relay must be installed. The relay may be

energized from the contacts on the boiler to allow

the pumps to be turned on and off with the demand.

The System pump connections are located on

terminal block 5 (5-6 on TB5) in the control panel.

(See Figure 19.) The System pump contacts are rated

for 120 VAC, 7.4 Amps. To use the contacts, power

must be supplied on one terminal with the other

terminal wired to the relay controlling the pump.
The DHW pump connections are located on terminal

block 5 (7-8 on TB5) in the control panel and are

rated for 120 VAC, 7.4 Amps. To use the contacts,

power must be supplied on one terminal, and the

other terminal wired to the relay controlling the

pump.

Advertising
This manual is related to the following products: