NeoTherm Boilers and Water Heaters

Page 115

Code Description

L or

H

Procedure

221

Unconfigured DHW (Domestic Hot

Water) high limit setpoint setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

222

Unconfigured Outlet high limit setpoint

setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

223

Unconfigured Stack limit setpoint

setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

224

Invalid DHW (Domestic Hot Water)

demand source setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

225

Invalid Flame threshold setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

226

Invalid Outlet high limit setpoint setting L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

227

Invalid DHW (Domestic Hot Water)

high limit setpoint setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

228

Invalid Stack limit setpoint setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

229

Invalid Modulation output setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

230

Invalid CH (Central Heat) demand

source setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.

231

Invalid Delta T limit delay setting

L

1. Return to Configuration mode and recheck

selected parameters, reverify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, replace module.