Page 16

SCHeD 40 metal PIPe CaPaCIty for 1.50 SPeCIfIC

GraVIty UnDIlUteD ProPane

NOMINAL PIPE SIZE @ 11” W.C. INLET AND 0.5” W.C.

PRESSURE DROP

SIZE 1/2” 3/4” 1” 1-1/4” 1-1/2” 2”

LENGTH MAXIMUM CAPACITY IN THOUSANDS OF BTU PER

HOUR

20 200 418 787 1616 2422 4664

40 137 287 541 1111 1664 3205

60

110 231 434

892

1337 2574

80

94

197 372

763

1144 2203

100

84

175

330

677

1014 1952

Notes:
1. Follow all local and national LP gas codes for line sizing and

equipment requirements.

2. Verify that inlet gas pressure remains between 4 and 13 inches

of water column before and during operation.

Source: ANSI Z223.1-80 National Fuel Gas code.

table 6D - Pipe Capacity for Propane

eQUIValent lenGtHS of StraIGHt PIPe for tyPICal

SCH 40 fIttInGS

NOMINAL PIPE SIZE

FITTING 1/2”

3/4”

1”

1-1/4”

1-1/2” 2”

LINEAR FEET

90° ELBOW 3.6

4.4

5.2

6.6

7.4

8.5

TEE 4.2 5.3 6.6

8.7

9.9 12

table 6B - equivalent Pipe lengths

neotHerm

natUral GaS

reQUIreD

CU FT

SIZE

/ HR.

1000 1000

to SIze PIPInG:

Measure linear distance from meter outlet to

last boiler. Add total input of all boilers and

divide by 1000 to obtain cu ft / hr required.

Add total equivalent length of fittings used

according to Table 6B. Align total length (pipe

and fittings) on left side column of Table 6C

with highest cubic feet of gas required.

notes:

Consult and confirm with Applicable Fuel

Gas Code before beginning work.

Verify gas inlet pressure is between 4 and 13

in W.C. before starting boiler.

table 6a - natural Gas requirements

SCH 40 metal PIPe CaPaCIty for 0.60 SPeCIfIC GraVIty

natUral GaS

NOMINAL PIPE SIZE @ 0.30” W.C. PRESSURE DROP

LENGTH 1/2”

3/4”

1”

1-1/4”

1-1/2”

2”

FT

CUBIC FEET OF GAS PER HOUR

20

92 190

350

730

1100

2100

40

130 245

500

760

1450

60

105 195

400

610

1150

80

90

170

350

530

990

100

150

305

460

870

table 6C - Pipe Capacity for natural Gas