6 water connections, 6a - nth units, 6a.1 hot supply connections – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 22: 6a.2 cold water make-up, 6a.3 freeze protection

Advertising
background image

LAARS Heating Systems

Page 18

The NeoTherm unit’s efficiency is higher with
lower return water temperatures.

Therefore, to

get the best low return temperature with multiple

boilers, pipe as shown in Figures 14 and 15.

6a.2 ntH Cold Water make-Up

1. Connect the cold water supply to the inlet

connection of an automatic fill valve.

2. Install a suitable back flow preventer between

the automatic fill valve and the cold water

supply.

3. Install shut off valves where required.
In some installations, a hot water heating boiler is

connected to heating coils located in an air handling

appliance where the coils may be exposed to

refrigerated air circulation. In these cases, the boiler

piping system must be equipped with flow control

valves or other automatic means to prevent gravity

circulation of the boiler water during the cooling

cycle.
A boiler installed above radiation level, or as

required by the authority having jurisdiction,

must be provided with a low water cutoff device

either as a part of the boiler or at the time of boiler

installation.

6a.3 ntH freeze Protection

WarnInG

Glycol must not be used in domestic hot water

applications. Refer to Section 6B.4 for instructions

on freeze protection for NTV units (domestic hot

water).

NeoTherm units may be installed indoors or

outdoors. If installed outdoors, the NTH unit

must never be installed in a location which may

experience freezing temperatures. If installed

indoors, and there is an event such as a power

outage, interruption of gas supply, failure of system

components, activation of safety devices, etc., this

may prevent a boiler from firing. Any time a boiler
is subjected to freezing conditions, and the boiler

is not able to fire, and/or the water is not able to
circulate, there is a risk of freezing in the boiler
or in the pipes in the system.

When water freezes,

it expands. This may result in bursting of pipes, or

damage to the boiler, and this could result in leaking

or flooding conditions.

ntH

PIPe SIze,

ntV

PIPe SIze,

SIze InCHeS

SIze InCHeS

1000 2

1000 2

table 9 - Water Connection Pipe Sizes

Section 6 -

Water ConneCtIonS

Section 6 is divided into two parts. Section
6A covers NTH units designed for hydronic
heating. Many installations include
indirect domestic hot water. Section 6B
covers NTV models, which are designed
exclusively for “volume water” domestic
hot water applications. Refer to the proper
section for instructions on installing and
piping your product. Refer to Table 9 for
the pipe sizes required.

Section 6a - ntH UnItS

6a.1 ntH System Piping:

Hot Supply Connections

note -This appliance must be installed in a closed

pressure system with a minimum of 12 psi (82.7

kPa) static pressure at the boiler.

The hot water piping should be supported by suitable

hangers or floor stands. Do not support the piping

with this appliance. The hangers used should allow

for expansion and contraction of copper pipe. Rigid

hangers may transmit noise through the system

resulting from the piping sliding in the hangers. We

recommend that padding be used when rigid hangers

are installed. Maintain 1” (2.5 cm) clearance to

combustibles for all hot water pipes.
Pipe the discharge of the relief valve (full size) to a

drain or in a manner to prevent injury in the event

of pressure relief. Install an air purger, an air vent,

a diaphragm-type expansion tank, a hydronic flow

check in the system supply loop, and any other

devices required by local codes. The minimum fill

pressure must be 12 psig (82.7 kPa). Install shutoff

valves where required by code.
Suggested piping diagrams are shown in Figures

11 through 15. These diagrams are meant only as

guides. Components required by local codes must be

properly installed.

Advertising
This manual is related to the following products: