LAARS Heating Systems

Page 64

In this example, we are still working with the

Primary control for Boiler 1. From the table,

you can see that this control should have a flap

valve ID of “1.” Enter the correct ID from

Table 5 in this field. The system will ask you

to login before you do this.

WarnInG

If the controller cannot find a signal from one

of the flap valves, the control system will act to

prevent backflow by energizing the blower of the

control with the bad flap valve. If this cannot be

done the control will not allow the whole system to

run. For this reason, it is important that all of the

flap valves be identified correctly.

7. At this point, you have set the flap valve ID’s

for both controllers on this boiler. Before you

leave, you must finish the verification process,

or the control system will not let the boiler

operate.

Press the Back arrow to return to the

Configuration screen.

Fig. 75 – Configuration Screen

8. In a moment, you will need to reset the

controller by pressing a button on the front of

the unit. See Fig. 76. The controllers for the

two boilers are mounted behind the door on

the front of the unit.

fig. 76 – reset Button on Controller

The control system allows 30 seconds to press

the reset button. Do not press the Reset button

yet! You will need to do this in a moment.

At this point, we just want to alert you to

something: In order to be able to reach the

controller within 30 seconds, it will be helpful

to open the door and slide out the control panel

first.

When you are ready, press the Verify button on

the Configuration screen.

9. To begin the verification, login to the system

and press Begin.

fig. 77 – edit Safety Data

10. The system will present a listing of a group

which includes the parameter you changed (the

flap valve ID). See Fig. 78.