2 venting – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 13

Advertising
background image

NeoTherm Boilers and Water Heaters

Page 9

3.2 Venting

WarnInG

Selection of improper vent materials for installations

that are installed in closets, or will be operated

in high ambient temperature levels, may lead to

property damage, personal injury, or death.

WarnInG

A 12” section of CPVC must be connected directly

to the boiler before a PVC vent system can be used.

Connecting PVC directly to the boiler’s flue collar

may cause vent failure, leading to property damage,

personal injury, or death.

WarnInG

Failure to use the appropriate vent material,

installation techniques, or glues and sealants could

lead to vent failure causing property damage,

personal injury or death.

WarnInG

All venting must be installed according to this

manual and any other applicable local codes,

including but not limited to, ANSI Z223.1/NFPA 54,

CSA B149.1, CSAB149.2 and ULC-S636. Failure to

follow this manual and applicable codes may lead to

property damage, severe injury, or death.

The flue temperature of the NeoTherm changes
dramatically with changes in operating water
temperature. Therefore, it is necessary to assess
the application of the boiler to determine the

required certified vent class. If the NeoTherm
is installed in an application where the ambient
temperature is elevated, and/or installed in
a closet/alcove, CPVC, polypropylene, or

stainless steel material is required. If the system
temperatures are unknown at the time of

installation, class IIC or higher venting material
is recommended.
The NeoTherm is a Category IV appliance and may

be installed with PVC, CPVC that complies with

ANSI/ASTM D1785 F441, or polypropylene that

complies with ULC-S636 Class 2C, or a stainless

steel venting system that complies with the UL

1738 Standard. (See Table 5.) The unit’s vent can

terminate through the roof, or through an outside

wall.
The use of polypropylene vent material has

been accepted by CSA for use with exhaust and

combustion. The polypropylene vent manufacturer

shall have ULCS636 Class 2C approval or higher

with a recognized listing agency for all components

used in the venting system. All components used

must be from the same manufacturer and designed

for use with exhaust temperatures of 195°F

(90°C) or higher. When installing polypropylene

vent systems, please, refer to the vent supplier’s

installation instructions for proper installation

techniques.

WarnInG

A 12” section (305 mm) of CPVC must be

connected directly to the boiler before a PVC vent

system can be used. Connecting PVC directly to the

boiler’s flue collar may cause vent failure, leading to

property damage, personal injury, or death.

When using PVC/CPVC for the vent material,

the first 12 inches (305 mm) of the vent must be

connected to the CPVC section included with the

NeoTherm unit. The CPVC vent section included

with the NeoTherm may be broken by CPVC fittings

if necessary, but never reduced in total length.

See Table 2 to select the appropriate vent pipe

diameter. The vent pipe must pitch upward, toward

the vent terminal, not less than 1/4” per foot, so

that condensate will run back to the NeoTherm to

drain. Route the vent pipe to the heater as directly as

possible. Seal all joints. Provide adequate hangers

as required in the venting system manufacturer’s

Installation Instructions. Horizontal portions of the

venting system must be supported to prevent sagging

and may not have any low sections that could trap

condensate. The unit must not support the weight of

the vent pipe. Please see Table 2 for proper diameter

vs. length allowed.

3.2.1

Common Venting

A single vent that is shared by multiple NeoTherm

units must be engineered by a competent venting

specialist, and could involve the selection of draft

inducing equipment, hardware and controls to

properly balance flue gas pressures. Do not common
vent NeoTherm units unless the vent system
meets this requirement. NeoTherm units are

never permitted to share a vent with Category I
appliances.

3.2.2

Condensate Drain trap

A condensate drain trap is included with the boiler

and is supplied to drain the boiler of condensate.

The vent condensate should be drained through a

drain tee located in the vent line. This will help

prevent excessive condensate from entering the

boiler condensate trap and preventing the boiler

from operating.
Connect a 3/4” PVC pipe between the drain

connection and a floor drain (or condensate pump if

a floor drain is not accessible).

Advertising
This manual is related to the following products: