About the “time of day” function – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 75

Advertising
background image

NeoTherm Boilers and Water Heaters

Page 71

When enabled, the Warm Weather Shutdown

feature will turn off the Central Heating

functions when the outdoor temperature

exceeds the setpoint. This prevents the system

from running when there is no need for heat.

Enable -

These options determine how quickly

the system shuts down after the outdoor

temperature rises above the setpoint. The

options are Shutdown immediately/ After

demand ends/ Disabled.

Setpoint -

If the outdoor temperature is higher than this,

the system will shut off the Lead/Lag Central

Heating functions.

13. Press the left-arrow or right-arrow until you see

the Rate Allocation screen (Fig. 92).

fig. 92 – rate allocation

As the load on the system increases, the first

boiler in the Lead/Lag chain will increase the

fan speed until it reaches a certain percentage

of the total output (the “base load”). At that

point, the controller will start the second boiler

in the lead/lag chain. See the explanation at

the beginning of this section and Fig. 51.

Base Load Common -

As the demand increases, this sets the point

at which the controller starts another burner

in the Lead/Lag chain.

To prevent short-cycling, the base load setting

should be set at the values shown in the table

below, or set to higher values.

about the “time of Day” function
If the “time of day” function is enabled, the control

system can be set to maintain different temperatures

for central heat and domestic hot water (other than

the normal setpoints) in the system at certain times of

the day. Normally this function is used to switch to

lower temperatures at night, when the central heating

or domestic hot water demand is reduced. When the

controller acting as the Lead/Lag Master receives a

time of day input, the controller shifts to the special

setpoints entered for central heat and domestic hot

water.

Number

of boilers

Installed

Base load min.

1

65%

2

50%

3

30%

4

30%

table 16 – Base load Settings

Advertising
This manual is related to the following products: