LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 114

Advertising
background image

LAARS Heating Systems

Page 110

Code Description

L or

H

Procedure

153

Combustion Pressure Off

H or

L

1. Check wiring and correct any errors.
2. Inspect the Combustion Pressure Switch to

make sure it is working correctly.
3. Reset and sequence the relay module.
4. During STANDBY and PREPURGE, measure

the voltage between J6 terminal 5 and L2 (N).

Supply voltage should be present. If not, the

lockout switch is defective and needs replacing.
5. If the fault persists, replace the relay module.

154

Purge Fan switch On

H or

L

1. Purge fan switch is on when it should be off.
2. Check wiring and correct any errors.
3. Inspect the Purge Fan switch J6 terminal 3 and

its connections. Make sure the switch is working

correctly and is not jumpered or welded.
4. Reset and sequence the relay module.
5. If the fault persists, replace the relay module.

155

Purge fan switch OFF

H or

L

1. Purge fan switch is off when it should be on.
2. Check wiring and correct any errors.
3. Inspect the Purge Fan switch J6 terminal 3 and

its connections. Make sure the switch is working

correctly and is not jumpered or welded.
4. Reset and sequence the relay module.
5. If the fault persists, replace the relay module.

156

Combustion pressure and flame ON

H or

L

1. Check that flame is not present in the

combustion chamber. Correct any errors.
2. Make sure that the flame detector is wired to

the correct terminal.
3. Make sure the F & G wires are protected from

stray noise pickup.
4. Reset and sequence the module, if code

reappears, replace the flame detector.
5. Reset and sequence the module, if code

reappears, replace the module.

157

Combustion pressure and flame OFF

L

1. Check that flame is not present in the

combustion chamber. Correct any errors.
2. Make sure that the flame detector is wired to

the correct terminal.
3. Make sure the F & G wires are protected from

stray noise pickup.
4. Reset and sequence the module, if code

reappears, replace the flame detector.
5. Reset and sequence the module, if code

reappears, replace the module.

158

Main valve ON

L

1. Check Main Valve terminal wiring and correct

any errors.
2. Reset and sequence the module. If fault

persists, replace the module.

Advertising
This manual is related to the following products: