6B.2 ntV Piping requirements

The water piping should be supported by suitable

hangers and floor stands. Do not support the piping

with this appliance. The hangers used should allow

for expansion and contraction of copper pipe. Rigid

hangers may transmit noise through the system

resulting from piping sliding in the hangers. We

recommend that padding be used when rigid hangers

are installed. Maintain 1” (2.5 cm) clearance to

combustibles for hot water pipes.
Pipe the discharge of the relief valve (full size) to

the drain or in a manner to prevent injury in the

event of pressure relief. Install a diaphragm-type

expansion tank, flow check, and shutoff valves

where needed or as required by code.
The piping should be installed so that each pump

supplies flow only to the heater to which it is

attached.

Section 6B - ntV UnItS

6B.1 ntV Water Quality

NTV water heaters must be installed in water

conditions of 10 gpg hardness or less, with a pH

range of 6.5 to 9.5 pH values outside of this range

may reduce the life expectancy of the product.

Operating the NTV in water with higher hardness

levels will cause heat exchanger fouling, erosion,

or corrosion, leading to premature component

failure, reduced efficiency, heat exchanger failure

or system failure. Failure of this type will not be

warranted. If the water in use exceeds the conditions

recommended, water softeners or other devices

should be installed to improve water quality.

fig. 16 - DHW Piping - one Heater, one Vertical tank

noteS:

1. Optional CWMU & recirculation line location.

2. Locate NTV DHW sensor or remote aquastat well

in lower 1/3 of tank.

3. Back flow preventer may be required - check local codes.

4. Thermal expansion tank may be required - check local codes.

WarnInG: This drawing shows

suggested piping configuration and

valving. Check with local codes and

ordinances for additional requirements.

Location

of pump

Expansion

tank

TPRV

2

Supply

Building

return

Expansion

tank

Cold

water

supply

4

4

1

3

3