NeoTherm Boilers and Water Heaters

Page 87

Label

Description

How to Reach

CH (Central

Heat) Pump

Cycle Count

CH pump cycle count. Can be written to a new

value (e.g. if the pump or controller is replaced).

Home screen/ Select controller/ Status

Summary screen/ Configure button/

Configuration List/ Select Statistics

Configuration line

CH (Central

Heat)

Setpoint

This setpoint is used when the time-of-day input

is off. If the outdoor reset function is active, this

setpoint provides one coordinate for the outdoor

reset curve. See the section for the CH Outdoor

Reset parameter.

If Lead/Lag enabled –

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen

CH (Central

Heat) TOD

(Time

of Day)

Setpoint

This setpoint is used when the time-of-day input

is on. If the outdoor reset function is active,

this Setpoint provides one coordinate for the

shifted outdoor reset curve, because the time-

of-day switch is on. See the section for the CH

Outdoor Reset parameter.”

If Lead/Lag enabled –

Home screen/ View Lead/Lag button/

Lead/Lag screen/ Lead/Lag Master

button/ Lead/Lag Master screen/

Configure button/ Lead/Lag Master

Configuration screen

DHW

(Domestic

Hot Water) D

Gain

This gain applied to the Differential term of the

PID equation for the DHW loop.

Home screen/ Select controller/ Status

Summary screen/ Configuration/

Domestic Hot Water Configuration

DHW

(Domestic

Hot Water)

Enable

This parameter determines whether the

Domestic Hot Water loop is enabled or disabled.

When it is disabled, the demand caused by the

DHW sensor is ignored. It may be disabled to

turn it off temporarily or because the application

does not use this feature.

Home screen/ Select controller/ Status

Summary screen/ Configuration/

Domestic Hot Water Configuration

DHW

(Domestic

Hot Water)

has priority

over CH

(Central

Heat)

This parameter determines the priority of

Domestic Hot Water vs. Central Heat call-for-

heat, when both of these are enabled and active.

(The DHW priority also may shift for a period

of time, as specified by DHW Priority time and

method parameters.)”

Home screen/ View Lead Lag/ Lead

Lag screen/ Lead Lag Master/ Lead Lag

Master screen/ Configure/ Lead Lag

Master Configuration screen/ Advanced

Settings/ Domestic Hot Water screen

DHW

(Domestic

Hot Water) I

gain

This gain applied to the Integral term of the PID

equation for the DHW loop.

Home screen/ Select controller/ Status

Summary screen/ Configuration/

Domestic Hot Water Configuration

DHW

(Domestic

Hot Water)

off hysteresis

The off hysteresis is added to the Domestic Hot

Water Setpoint to determine the temperature at

which the DHW burner demand turns off.

Home screen/ Select controller/ Status

Summary screen/ Configuration/

Domestic Hot Water Configuration

DHW

(Domestic

Hot Water)

on hysteresis

The on hysteresis is subtracted from the

Domestic Hot Water Setpoint to determine the

temperature at which the DHW burner demand

turns on.

Home screen/ Select controller/ Status

Summary screen/ Configuration/

Domestic Hot Water Configuration

DHW

(Domestic

Hot Water) P

gain

This gain applied to the Proportional term of the

PID equation for the DHW loop.

Home screen/ Select controller/ Status

Summary screen/ Configuration/

Domestic Hot Water Configuration

DHW

(Domestic

Hot Water)

priority

override time

If this parameter is non-zero then a Domestic

Hot Water demand will shift its priority vs.

other demand sources according to the specified

time. The priority override timing is reset when

demand from the DHW source turns off.

Home screen/ View Lead Lag/ Lead

Lag screen/ Lead Lag Master/ Lead Lag

Master screen/ Configure/ Lead Lag

Master Configuration screen/ Advanced

Settings/ Domestic Hot Water screen