Job j - install system sensor and adjust setpoint – LAARS NeoTherm NTV1000 - Install and Operating Manual User Manual

Page 76

Advertising
background image

LAARS Heating Systems

Page 72

The input for the Time of Day function must be wired

to pins 2 and 3 on connector J10.

fig. 93 – Connections for “time of Day” function

Job J - Install System Sensor and adjust

Setpoint

(This is a Lead/Lag function – do this once for the whole Lead/
Lag system. Make the connections to the controller set up as the
Lead/Lag Master – usually the Primary controller on Boiler 1.)

1. Install the System sensor at the location shown

in Fig. 94. Connect the System sensor to the

System terminals on the controller acting as

the Lead/Lag Master (usually the Primary

controller on Boiler 1.) Use terminals 3 and 4

on TB6.

2. Adjust the Lead/Lag Central Heat Setpoint

to the desired temperature to be used by the

system.

How to get there – Adjust CH Setpoint

Home Page <Press View Lead Lag button> Lead Lag

Screen <Press Lead Lag Master button> Lead Lag Screen
<Press Configure button> Lead Lag Master Configuration
Screen

Line 2 = CH Setpoint

fig. 94 – mounting location for System Sensor

Job K - Set lead lag outdoor reset and

Warm Weather Shutdown

(This is a Lead/Lag function – do this once for the whole Lead/
Lag system. Use the controller set up as the Lead/Lag Master –
usually the Primary controller on Boiler 1.)

For more information on the outdoor reset function,

see the explanation which follows.

1. Install the outdoor air temperature sensor and

make the connections to the outdoor air sensor

terminals on the controller acting as the Lead/

Lag Master (usually the Primary controller on

Boiler 1.) Use terminals 1 and 2 on TB7.

2. Set the outdoor reset and warm weather

shutdown parameters as desired.

How to get there – Outdoor Reset Screen and Warm

Weather Shutdown Screen

Home Page <Press View Lead/ Lag button> Lead/ Lag

Screen <Press Lead/ Lag Master button> Lead/ Lag
Screen <Press Configure button> Lead/ Lag Master
Configuration Screen <Press Advanced Settings button>

Select the Outdoor Reset Screen or the Warm Weather

Shutdown Screen

fig. 95 – outdoor reset

For a detailed explanation of the Outdoor Reset

function, see the section titled “About Outdoor

Reset” which follows.

Pins 2 and 3 on

connector J10

Advertising