Setting up the dump valve (where fitted), Setting the dump off delay time, Setting the dumping cycle times – Bonaire Comfort Control - RF/LV User Manual

Page 44

Advertising
background image

Multi-Appliance Comfort Control

Controls- Installation / Setup / Commissioning

S

ETTING UP THE

D

UMP

V

ALVE

(W

HERE

F

ITTED

)

Dump valve settings have two parts to the setup.

Setting the dumping cycle time

Setting the Dump OFF delay time.


S

ETTING THE

D

UMP

OFF

D

ELAY

T

IME

.

Dump OFF Delay Time gives the option for immediate dumping of
the water from the Tank or a one hour delay after the unit has been
turned OFF. Setting the 1 hour delay is preferable if the unit is going
to be used in thermostat (AUTO) mode. To set the 1 hour delay:

1. Make sure the unit is in MANUAL mode and is set to COOL

FRESH AIR.

2. Press the ENTER button and the MANUAL/AUTO buttons

together for 10 seconds. Press the ENTER button first. The
word OPT and some numbers will flash on the screen.

3. Using the ▼ or ▲buttons make the top number read 00.

Press ENTER.

4. Using the ▼ or ▲ buttons change the number of the second

line to 01. Press ENTER.

The one hour delay is now set.


S

ETTING THE

D

UMPING

C

YCLE

T

IMES

1. Make sure the unit is in MANUAL mode and is set to COOL

FRESH AIR.

2. Press the ENTER button and the MANUAL/AUTO buttons

together for 10 seconds. Press the ENTER button first. The
word OPT and some numbers will flash on the screen.

3. Using the ▼ or ▲buttons make the top number reads 01.

Press ENTER.

4. Using the ▼ or ▲buttons change the number of the second

line to hourly required between dumping the water from the
tank. Press ENTER. Dumping Cycles can be 0, 1, 2, 4, 8, 12,
24 hours.

The dumping cycle times have now been set.



Comfort Control - PNE