Certifications, Safety, Chapter 19 certifications – Digi CM User Manual

Page 151

Advertising
background image

Certifications

Chapter 18

151

Safety

•

US: UL1950

•

Canada: CSA 22.2 No. 60950

•

Europe: EN60950 (CB Scheme Report)

Working Inside the Digi CM

NOTICE: Do not attempt to service the Digi CM yourself, except when
following the instructions from Digi Technical Support personnel. In such a
case, first perform the following actions:

•

Turn off the Digi CM.

•

Ground yourself by touching an unpainted metal surface at the back of the
equipment before touching anything inside your equipment.

Replacing the Battery

A coin-cell battery maintains date and time information. If you have to
repeatedly reset time and date information after turning on your Digi CM,
replace the battery.

CAUTION: A new battery can explode if it is incorrectly installed. Replace the
3 Volt CR2032 battery only with the same or equivalent type recommended by
the battery manufacturer. Discard used batteries according to the battery
manufacturer’s instructions.

Rack Mounting Installation Considerations

For a rack setup with forced air, the device can run 0-55° C with no extra
space above or below the device (default design of the Digi CM Rack provides
1/16” = 2mm between devices).

For a rack setup with no forced air, make sure that the air in-between devices
does not get warmer than 55°C by the following measures:

•

Providing space between the devices, or

•

controlling the ambient temperature on the rack.

•

Distribute weight evenly in the rack to avoid overloading.

•

Check equipment nameplate ratings before connecting to the supply circuit
to avoid overloads which may damage over-current protection devices and
supply wiring.

•

Maintain reliable earthing for rack-mounting equipment, especially for
supply connections.

Chapter 18

C e r t i f i c a t i o n s

Advertising