Setting the mpi-c, Setting, Mpi-c – Gasboy FuelOmat system 8 Popt Commverter User Manual
Page 126

8 Port CommVerter Operation and Installation Manual
122
The final formula for a Flow Rate of 200 Liter/Minute, is therefore:
PW
µSec
= 150000/F
Pulse/Lit
3.
SETTING THE MPI-C
The following values are calculated for some representative factors:
F
Pulse
Liter
PPS
Pulse
Second
PW
Msec
Actual
PW
µSec
10
33.33
15.000
1000
25
83.33
6.000
1000
50
166.67
3.000
1000
100
333.33
1.500
1000
200
666.67
0.750
750
500
1666.67
0.300
300
1000
3333.33
0.150
150
2000
6666.67
0.075
100
5000
16666.67
0.030
100
The “Actual Pulse Width” range will limited to MaxPW =1000 and MinPW=100 microseconds.
The pulse width will be sent to the MPI-C by the Pump Server. In dual mode, the MPI-C will use
the received PW form either channel, for both channel. It is the responsibility of the Pump-Server to
send the lower PW value to either channel.
The default value of the MPI-C is PW=1000.