45

Figure 44 Installing an MPU (for the S12508 and S12518)

Connecting power cords

Follow these guidelines before connecting power cords:

For lightning protection, the AC power should be led through an external lightning device into an
S12500 switch. For more information, see "Appendix D Lightning protection."

Make sure the power switch on the power frame is in the OFF position.

For personal and switch safety, do not connect the power cords with the power. Power off the
grounding strip, connect the power cords, power on the grounding strip, and then power on the

switch.

Connecting an AC power cord

Each socket on a PEM (LSTM2PEMC6) corresponds to a power supply slot. Sockets numbered 1 through

6 provide power for the power supplies in slots 1 through 6, respectively. If slot 1 is installed with a power

supply, the number 1 receptacle on the PEM must be connected to a power source with an AC power

cord to make the power supply operate properly.

CAUTION:

Typically 10 A busbars are available in the equipment room but the PEM on the S12500 (LSTM2PEMC6)
requires a 16 A power cord (AC), so you need to use a 16 A busbar, and make sure the AC power supply

system can provide enough power. For AC power cords used in different countries or regions, see
"Appendix A Technical specifications."

To connect power cords:

1.

Remove the strain-relief screws of the power cord retention clip, and remove the retention clip.