Installing fiber management tray (optional) – H3C Technologies H3C S12500 Series Switches User Manual

Page 70

Advertising
background image

60

3.

Insert one end of the plug of the SFP+ cable horizontally into the SFP+ slot on the switch and the

other end of the plug into the SFP+ slot of the peer device.

NOTE:

SFP+ cables are hot swappable.

When connecting an SFP+ cable, make sure the bend radius of the cable is no less than eight times of
the diameter of the cable.

Installing fiber management tray (optional)

NOTE:

The installation method described below is based on an N68 rack. The installation procedure is only for
your reference if you use a non-N68 rack.

A fiber management tray (FMT) is installed in a rack for winding redundant fibers between the S12500

and other devices.

Preparations
Confirm the following prerequisites:

{

The rack is fixed.

{

The switch is installed.

The installation involves the following materials:

{

FMT

{

M5×10 self-tapping screws (two screws for one FMT)

Installation procedure
To install the fiber management tray:

a.

Align the FMT and the installation holes on the column of the rack.

b.

Use a Phillips screwdriver to fix each FMT with two M5×10 self-tapping screws.

Figure 59 Installing FMTs