Problem

Cause and corrective measure

No measured values for the con-
nected temperature sensor are shown
on the display.

The temperature sensor is not correctly connected.
Corrective measures:

• Ensure that the temperature sensor is correctly

connected (see the Cluster Controller installation
manual).

No measured values for the con-
nected irradiation sensor are shown
on the display.

If no measured values are displayed for the irradiation
sensor, either the characteristic curve of the irradiation sen-
sor is not configured or the irradiation sensor is not cor-
rectly connected.
Corrective measures:

• Ensure that the characteristic curve of the irradiation

sensor is configured (see Section 7.1, page 44).

• Ensure that the irradiation sensor is correctly

connected (see the Cluster Controller installation
manual).

Though it is not connected, a mea-
sured value of up to 2.2 V for pin
group Analog voltage input 4 is
shown on the display and the user in-
terface.

If no sensor is connected to the pin group Analog volt-
age input 4
, a measured value for this pin group of up to
2.2 V will nevertheless be shown on the display and the
user interface of the Cluster Controller.
Corrective measures:

• In order for a measured value of 0 V to be displayed

for the pin group Analog voltage input 4 when it is
not connected, place a jumper wire between pins B5
and B7 in terminal X8.

Login

Problem

Cause and corrective measure

The login page does not open and the
status LED (

) is flashing red.

The Cluster Controller could not start correctly. A system
error has occurred.
Corrective measures:

• Disconnect the Cluster Controller from the voltage

supply and reconnect it to the voltage supply. Note
that this can lead to loss of system data.

• If the problem persists, contact the Service .

18 Troubleshooting