USB and Update

Problem

Cause and corrective measure

The update via the USB data carrier
does not start.

There are no update files on the USB data carrier or the
update files on the USB data carrier are not located in the
UPDATE directory.
Corrective measures:

• Save the desired update files onto the USB data

carrier in the UPDATE directory and connect the
USB data carrier to USB port 2 of the
Cluster Controller.

The Cluster Controller does not write
any data to the USB data carrier.

The USB data carrier is connected to USB port 2. The
Cluster Controller only writes data to USB data carriers
that are connected to USB port 1.
Corrective measures:

• Connect the USB data carrier to USB port 1. Note

that the USB data carrier must not be write-protected.

No inverters or not all inverters report
back with the version number of the
sent update file.

If you have configured the automatic update and the Inter-
net connection was interrupted or is interrupted, the up-
date file may not have been correctly downloaded from
the Internet.
Corrective measures:

• Ensure that an Internet connection is established. The

automatic update for the inverters starts again on the
following day.

• To start the update directly, perform a manual update

(see Section 14.2.2, page 80).

The USB data carrier was removed from the Cluster Con-
troller during the update process.
Corrective measures:

• Reconnect the USB data carrier to USB port 2 and

perform a manual device update (see
Section 14.2.2, page 80)
.

18 Troubleshooting

SMA Solar Technology AG / SMA America, LLC

User Manual