background image

LED

Status

Cause and corrective measure

Status (

)

flashing yellow

An update of the Cluster Controller or the con-
nected devices is currently taking place.

The active power limitation is active and the de-
fault value is above 0% and below 100%.

The reactive power setpoint is active. The default
value is not 0% or the displacement power factor
cos φ is below 1.

glowing red

The active power limitation is active and the de-
fault value is 0%.

At least one device has the status Error.
Corrective measures:

• Check the Cluster Controller event log (see

Section 9.1, page 55).

• Refer to the device documentation.

Status (

)

glowing red

Communication with all devices is disturbed. There
is a problem in the LAN.
Corrective measures:

• Ensure that the network cables are correctly

connected (see the Cluster Controller
installation manual).

• Check whether the network components,

network cables or connectors are defective
or damaged. Replace defective or damaged
network components, network cables or
connectors.

• Check whether the network settings of the

individual network components are correct.
Adapt the network settings if required.

• Restart the Cluster Controller if required.

Disconnect the Cluster Controller from the
voltage supply and reconnect it to the
voltage supply.

• If required, assign a fixed IP address for the

Cluster Controller (see Section 17.1.1, page
90).

• If the problem persists, contact the network

administrator.

18 Troubleshooting