Communication

Problem

Cause and corrective measure

Communication with at least one de-
vice is disturbed.

There may be a disturbance in the device.
Corrective measures:

• Check the Cluster Controller event log (see

Section 9.1, page 55).

• Refer to the device documentation.

The Cluster Controller may not be connected to the de-
vice.
Corrective measures:

• Ensure that the network cables are correctly

connected (see the Cluster Controller installation
manual).

• Check whether the network components, network

cables or connectors are defective or damaged.
Replace defective or damaged network components,
network cables or connectors.

• Check whether the network settings of the individual

network components are correct. Adapt the network
settings if required.

• If the problem persists, contact the network

administrator.

Problem

Cause and corrective measure

Communication with all devices is dis-
turbed.

There is a problem in the LAN.
Corrective measures:

• Ensure that the network cables are correctly

connected (see the Cluster Controller installation
manual).

• Check whether the network components, network

cables or connectors are defective or damaged.
Replace defective or damaged network components,
network cables or connectors.

• Check whether the network settings of the individual

network components are correct. Adapt the network
settings if required.

• Restart the Cluster Controller. Disconnect the

Cluster Controller from the voltage supply and
reconnect it to the voltage supply.

• If the problem persists, contact the network

administrator.

18 Troubleshooting

SMA Solar Technology AG / SMA America, LLC

User Manual

ClusterController-BA-en-14