13.2 Setting Parameters for Grid Management Services in

the Inverters

To enable the inverters in the system to implement the grid management service setpoints of the
Cluster Controller, you will first need to set the corresponding parameters in the inverters.

Requirement:

☐ You must have received a personal SMA Grid Guard code (application form for the

SMA Grid Guard code available at www.SMA-Solar.com, for further information on the
SMA Grid Guard code, see Section 15.5, page 87).

Procedure:

1. Log in to the Cluster Controller as Installer.

2. Select the SMA Grid Guard symbol (

) in the status bar.

☑ This opens the SMA Grid Guard dialog.

3. In the field Individual access code, enter the personal SMA Grid Guard code.
4. Select [OK].

☑ The SMA Grid Guard mode is activated. In the system tree, updating the symbols for

access rights (SMA Grid Guard symbol and padlock symbol) can take up to two minutes.

5. Select the system in the system tree and select the menu Settings in the device menu.
6. Select the parameter group System & device control.
7. Select [Edit].
8. To enable the inverters to receive and implement setpoints for active power limitation from the

Cluster Controller, proceed as follows:

• Select the group Configuration of feed-in management.
• In the dropdown list Operating mode Active power, select Act. power lim. via PV

system ctrl.

9. To enable the inverters to receive and implement setpoints for reactive power from the

Cluster Controller, proceed as follows:

• Select the group Conf. of the static voltage maint. at Q on demand.
• Select the desired entry in the dropdown list Operating mode of static voltage

stabilisation.

Setting

Explanation

cosPhi, specified by PV system
control

The inverter only implements cos Phi setpoints.

Q specified by PV system control

The inverter only implements Reactive power in %
setpoints.

cos Phi or Q specification through
optimum PV system control

The inverter implements cos Phi setpoints as well as
Reactive power in percent setpoints.

10. Select [Save].