18.1 LED States

18.1.1 Operation LEDs

Assignment of the Status LED (

):

The status LED can display the following statuses:

• Status of the Cluster Controller
• Status of the connected inverters
• Status of the system communication
• Status of the grid management services

If the status LED is not glowing green after commissioning, refer also to the event log of the
Cluster Controller to determine the precise cause of the error. The details of each error are logged
in the event log (see Section 9.1, page 55).

LED

Status

Cause and corrective measure

All

off

The Cluster Controller is not connected to the volt-
age supply.
Corrective measures:

• Connect the Cluster Controller to the voltage

supply (see the Cluster Controller installation
manual).

The voltage supply is reverse-connected or the
power supply unit is defective.
Corrective measures:

• Ensure that the voltage supply is correctly

connected (see the Cluster Controller
installation manual).

• If the voltage supply is connected correctly,

replace the power supply unit.

Power (

) and status

(

)

Power glowing
red, status glow-
ing yellow or red

The voltage supply is too low.
Corrective measures:

• Ensure that the connected voltage supply is

sufficient (see the Cluster Controller
installation manual).

• If the problem persists, contact the Service

(see Section 21, page 116).

Power (

)

glowing green

The start procedure is complete. The Cluster Con-
troller is ready for operation.