Parameter

Explanation

Start setpoint active power limita-
tion

Lower limit for the setpoint for the active power limitation re-
lated to the inverter parameter Set active power limit or
Pmax

End setpoint active power limita-
tion

Upper limit for the setpoint for the active power limitation re-
lated to the inverter parameter Set active power limit or
Pmax

For reactive power setpoint in %:
Start setpoint reactive power

Lower limit for the setpoint for the reactive power setpoint re-
lated to the inverter parameter Set active power limit or
Pmax

For reactive power setpoint in %:
End setpoint reactive power

Upper limit for the setpoint for the reactive power setpoint re-
lated to the inverter parameter Set active power limit or
Pmax

For setpoint cos Phi:
Cos Phi start setpoint

Lower limit for the setpoint of the displacement power factor
cos φ

For setpoint cos Phi:
Cos Phi end setpoint

Upper limit for the setpoint of the displacement power factor
cos φ

For setpoint cos Phi:
Excitation type

Direction of phase shift

4 User Interface of the Cluster Controller