Problem

Cause and corrective measure

The login page does not open.

There is a problem in the LAN.
Corrective measures:

• Ensure that the network cables are correctly

connected to the Cluster Controller (see the
Cluster Controller installation manual).

• Check whether the network components, network

cables or connectors are defective or damaged.
Replace defective or damaged network components,
network cables or connectors.

• Check whether the network settings of the individual

network components are correct. Adapt the network
settings if required.

• Restart the Cluster Controller. Disconnect the

Cluster Controller from the voltage supply and
reconnect it to the voltage supply. Note that this can
lead to loss of system data.

• If the problem persists, contact the network

administrator.

The login page does not open.

If the Cluster Controller is accessed via the Internet, there
may not currently be an Internet connection or the port for-
warding to the Cluster Controller from the router may be
missing or may have been set up incorrectly.
Corrective measures:

• In the event of interrupted Internet connection, restore

the Internet connection.

• If port forwarding has not been set up, set up port

forwarding to the Cluster Controller on the router.

• If port forwarding has already been set up on the

router, ensure that it is correct.

Login to the user interface has failed.

The system password has been entered incorrectly four
times. Access to the Cluster Controller is suspended for
15 minutes.
Corrective measures:

• Wait 15 minutes, then log in with the correct system

password.

18 Troubleshooting

SMA Solar Technology AG / SMA America, LLC

User Manual

ClusterController-BA-en-14