10 Appendix 2 Parameter Cross Reference

10

Appendix 2 Parameter Cross Reference

‹

Parameter Setting Procedure

1.

This document lists the information needed to upgrade from F7 to a new A1000 drive. The A1000 drive must be set for Heavy Duty. First, set A1000
parameter C6-01 to 0.

2.

Check all F7 parameters that have been changed from their default settings by using the Modified Constants Menu.

3.

Set the same control mode used for F7 to A1000.

4.

Set parameters as described in this section.

Note: Default Values in the table below are listed for A1000 200 V Class 0.4 kW Drive Using Open Loop Vector Control

Table 18 Parameter Cross Reference

Parameter Name

F7

A1000

Setting

Parameter

Default

Parameter

Default

F7

A1000

Environment
Settings

Language
Selection

A1-00

0

A1-00

0

A1-00

A1-00

0: English

0: English

1: Japanese

1: Japanese

2: German

2: German

3: French

3: French

4: Italian

4: Italian

5: Spanish

5: Spanish

6: Portuguese

6: Portuguese

7: Chinese

Access Level
Selection

A1-01

2

A1-01

2

A1-01

A1-01

0: Operation only
(monitors only)

0: Operation only (monitors only)

1: User Parameters

1: User Parameters *

2: All parameters

2: All parameters

*Set parameters A2-01 through A2-32

Environment
Settings

Control Method
Selection

A1-02

2

A1-02

2

A1-02

A1-02

0: V/f Control

0: V/f Control

1: V/f w/PG Control

1: V/f w/PG Control

2: Open Loop Vector

2: Open Loop Vector

3: Flux Vector

3: Closed Loop Vector

5: Open Loop Vector for PM

6: Advanced Open Loop Vector for PM

7: Closed Loop Vector for PM

Initialize
Parameters

A1-03

0

A1-03

0

A1-03

A1-03

0: No initialization

0: No initialization

1110: User initialize

1110: User initialize

2220: 2-wire sequence

2220: 2-wire sequence

3330: 3-wire sequence

3330: 3-wire sequence

5550: Reset OPE04

Password

A1-04

0

A1-04

0000

Password Setting

A1-05

0

A1-05

0000

User Parameters

A2-01 to

A2-32

A2-01 to

A2-32

If setting A1-01 to 1, refer to the manual and set parameters A2-01 top A2-32.