10 appendix 2 parameter cross reference – Yaskawa F7 to A1000 User Manual

Page 49

Advertising
background image

10 Appendix 2 Parameter Cross Reference

YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide

49

MEMOBUS
Communication

Drive Node
Address

H5-01

1F

H5-01

1F

Communication
Speed Selection

H5-02

3

H5-02

3

H5-02

H5-02

0: 1200 bps

0: 1200 bps

1: 2400 bps

1: 2400 bps

2: 4800 bps

2: 4800 bps

3: 9600 bps

3: 9600 bps

4: 19200 bps

4: 19200 bps

5: 38400 bps

6: 57600 bps

7: 76800 bps

8: 115200 bps

Communication
Parity Selection

H5-03

0

H5-03

0

H5-03

H5-03

0: No parity

0: No parity

1: Even parity

1: Even parity

2: Odd parity

2: Odd parity

Stopping Method
After
Communication
Error

H5-04

3

H5-04

0

H5-04

H5-04

0: Ramp to stop

0: Ramp to stop

1: Coast to stop

1: Coast to stop

2: Fast Stop

2: Fast Stop

3: Alarm Only

3: Alarm Only

Communication
Fault Detection
Selection

H5-05

1

H5-05

0

H5-05

H5-05

0: Disabled

0: Disabled

1: Enabled

1: Enabled

Drive Transmit
Wait Time

H5-06

5 ms

H5-06

5 ms

RTS Control
Selection

H5-07

1

H5-07

1

H5-07

H5-07

0: Disabled
(RTS always on)

0: Disabled
(RTS always on)

1: Enabled
(RTS enabled during send
only)

1: Enabled
(RTS enabled during send only)

Unit Selection for
MEMOBUS
Register 0025H

H5-10

0

H5-10

0

H5-10

H5-10

0: 0.1 V units

0: 0.1 V units

1: 1 V units

1: 1 V units

Pulse Train I/O

Pulse Train Input
Function Selection

H6-01

0

H6-01

0

H6-01

H6-01

0: Frequency reference

0: Frequency reference

1: PID feedback value

1: PID feedback value

2: PID setpoint value

2: PID setpoint value

3: V/f Control with Simple PG feedback

Pulse Train I/O

Pulse Train Input
Scaling

H6-02

1440 Hz

H6-02

1440 Hz

Pulse Train Input
Gain

H6-03

100.0 %

H6-03

100.0 %

Pulse Train Input
Bias

H6-04

0.0 %

H6-04

0.0 %

Pulse Train Input
Filter Time

H6-05

0.10 s

H6-05

0.10 s

Pulse Train
Monitor Selection

H6-06

2

H6-06

102

H6-06

H6-06

01: Frequency reference

101: Frequency reference

02: Output frequency

102: Output frequency

05: Motor speed

105: Motor speed

20: Output frequency after
soft start

116: Output frequency after soft start

24: PID feedback

501: PID feedback

36: PID input amount

502: PID input amount

Pulse Train
Monitor Scaling

H6-07

1440 Hz

H6-07

1440 Hz

Parameter Name

F7

A1000

Setting

Parameter

Default

Parameter

Default

F7

A1000

Advertising