10 appendix 2 parameter cross reference – Yaskawa F7 to A1000 User Manual

Page 42

Advertising
background image

10 Appendix 2 Parameter Cross Reference

42

YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide

Multi-Function
Relay Input

Multi-Function
Digital Input
Terminal S1
Function Selection

H1-01*

40

Use this

setting

*Input functions for terminals S1 and S2 are fixed in F7, but multi-functional in
A1000.

H1-01 to H1-06 (S3-S8)

H1-01 to H1-08 (S1-S8)

0: 3-wire sequence

0: 3-wire sequence

1: LOCAL/REMOTE
selection

1: LOCAL/REMOTE selection

2: Option/Drive selection

2: External Ref. ½ Selection
b1-15*
b1-16*
3: Option card
3: Option card
*Used when closed. When open, source is determined
by b1-01 and b1-02

3: Multi-Step Frequency
Ref. 1

3: Multi-Step Frequency Ref. 1

4: Multi-Step Frequency
Ref. 2

4: Multi-Step Frequency Ref. 2

Multi-Function
Digital Input
Terminal S2
Function Selection

H1-02

*

41

Use this

setting

5: Multi-Step Frequency
Ref. 3

5: Multi-Step Frequency Ref. 3

6: Jog freq ref selection

6: Jog freq ref selection

7: Accel/Decel Time
Selection 1

7: Accel/decel time selection 1

8: External Baseblock
(N.O.)

8: External Baseblock (N.O.)

9: External Baseblock
(N.C.)

9: Baseblock command (N.C.)

A: Accel/decal Ramp
Hold

A: Accel/decel ramp hold

B: External overheat alarm
(OH2)

B: Drive overheat alarm

Terminal S3
Function Selection

H1-01

24

H1-03

24

C: Terminal A2 Enable

C: Analog Terminal input selection

D: V/f with PG Disabled

D: PG encoder disable

E: ASR integral reset

E: ASR integral reset

F: Not used

F: Through-mode

10: MOP Increase

10: Up command

11: MOP Decrease

11: Down command

12: FWD jog

12: FWD jog

13: REV jog

13: REV jog

Terminal S4
Function Selection

H1-02

14

H1-04

14

14: Fault Reset

14: Fault Reset

15: Fast Stop (N.O.)

15: Fast Stop (N.O.)

16: Motor 2 selection

16: Motor 2 selection

17: Fast Stop (N.C.)

17: Fast Stop (N.C.)

18: Timer function input

18: Timer function input

19: PID disable

19: PID disable

1A: Accel/decel time
selection 2

1A: Accel/decel time selection 2

1B: Program Lockout

1B: Program Lockout

Parameter Name

F7

A1000

Setting

Parameter

Default

Parameter

Default

F7

A1000

Advertising