11 appendix 3 terminal size and wire gauge – Yaskawa F7 to A1000 User Manual

Page 61

Advertising
background image

11 Appendix 3 Terminal Size and Wire Gauge

YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide

61

A1000

4A0011

R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3,
-, +1, +2, B1, B2

M4

1.2 to 1.5

(10.6 to 13.2)

14 to 10

12, 14 (T1-3)

M4

1.2 to 1.5

(10.6 to 13.2)

14 to 10

10

F7

45P5

R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3,
-, +1, +2, B1, B2

M4

1.2 to 1.5

(10.6 to 13.2)

12 to 10

12

M4

1.2 to 1.5

(10.6 to 13.2)

14 to 10

14

A1000

4A0018

R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3,
-, +1, +2

M4

1.2 to 1.5

(10.6 to 13.2)

12 to 6

10

B1, B2

M4

1.2 to 1.5

(10.6 to 13.2)

12 to 6

M5

2 to 2.5

(17.7 to 22.1)

14 to 10

10

F7

47P5

R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3,
-, +1, +2, B1, B2

M4

1.8

(15.6)

10

10

M4

1.8

(15.6)

12 to 10

12

A1000

4A0023

R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3,
-, +1, +2

M4

1.2 to 1.5

(10.6 to 13.3)

10 to 6, 12 to 6 (-, +1, +2)

10

B1, B2

M4

1.2 to 1.5

(10.6 to 13.3)

12 to 10

M5

2 to 2.5

(17.7 to 22.1)

12 to 10

10

F7

4011

R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3,
-, +1, +2, B1, B2

M5

2.5

(21.99)

10 to 6

8

M5

2.5

(21.99)

10 to 6

10

A1000

4A0031

R/L1, S/L2, T/L3,
-, +1, +2

M5

2 to 2.5

(17.7 to 22.1)

8 to 6, 10 to 6 (-, +1, +2)

8

U/T1, V/T2, W/T3

M5

2 to 2.5

(17.7 to 22.1)

10 to 6

8

B1, B2

M5

2 to 2.5

(17.7 to 22.1)

10 to 8

M6

4 to 6

(35.4 to 53.1)

10 to 8

8

F7

4015

R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3,
-, +1, +2, B1, B2

M5

2.5

(21.99)

8 to 6

8

M5, M6

2.5 (21.99), 4.0 to 5.0

(35.2 to 43.99)

10 to 6

10

A1000

4A0038

R/L1, S/L2, T/L3,
U/T1, V/T2, W/T3

M5

2 to 2.5

(17.7 to 22.1)

8 to 6

6, 8 (T1-3)

-, +1, +2

M5

2 to 2.5

(17.7 to 22.1)

8 to 6

B1, B2

M5

2 to 2.5

(17.7 to 22.1)

10 to 8

M6

4 to 6

(35.4 to 53.1)

10 to 6

6

Series

Model

Terminal Signal

Terminal

Screw

Tightening Torque

N m (lb.in.)

Wire Range AWG,

kcmil

Recommended

Gauge AWG, kcmil

Advertising