10 appendix 2 parameter cross reference – Yaskawa F7 to A1000 User Manual

Page 50

Advertising
background image

10 Appendix 2 Parameter Cross Reference

50

YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide

Motor Protection
Function

Motor Overload
Protection
Selection

L1-01

1

L1-01

1

*

L1-01

L1-01

0: Disabled

0: Disabled

1: Standard fan cooled

1: General-purpose motor

2: Standard blower cooled

2: Drive-dedicated motor with a speed range of 1:10

3: Vector motor

3: Vector motor with a speed range of 1:100

4: PM motor with variable torque

5: PM motor with constant torque control

6: General purpose motor (50 Hz)

*Determined by parameter A1-02

Motor Overload
Protection Time

L1-02

8.0 min.

L1-02

1.0 min.

Motor Overheat
Alarm Operation
Selection

L1-03

3

L1-03

3

L1-03

L1-03

0: Ramp to stop

0: Ramp to stop

1: Coast to stop

1: Coast to stop

2: Fast Stop

2: Fast Stop

3: Alarm Only

3: Alarm Only

Motor Protection
Function

Motor Overheat
Fault Operation
Selection

L1-04

1

L1-04

1

L1-04

L1-04

0: Ramp to stop

0: Ramp to stop

1: Coast to stop

1: Coast to stop

2: Fast Stop

2: Fast Stop

Motor Temperature
Input Filter Time

L1-05

0.20 s

L1-05

0.20 s

Momentary Power
Loss Process

Momentary Power
Loss Detection/
Operation
Selection

L2-01

0

L2-01

0

L2-01

L2-01

0: Disabled

0: Disabled

1: Power Loss Ride Thru
Time

1: Recover within the time set in L2-02

2: CPU Power Active

2: Recover as long as CPU Power Active

3: KEB deceleration for time set in L2-02

4: KEB deceleration as long as CPU has power.

5: KEB deceleration to stop.

Momentary Power
Loss Ride-Thru
Time

L2-02

*

L2-02

*

*Dependent on kVA and parameters C6-01 and o2-04

Momentary Power
Loss Minimum
Baseblock Time

L2-03

*

L2-03

*

*Dependent on kVA and parameters C6-01 and o2-04

Momentary Power
Loss Voltage
Recovery Ramp
Time

L2-04

*

L2-04

*

*Dependent on kVA and parameters C6-01 and o2-04

Undervoltage
Detection Level

L2-05

190 V

L2-05

190 V

380 V for a 400 class drive.
But if E1-01 is set lower than 400, then for set 350 V for A1000.

KEB Deceleration
Time

L2-06

0.0 s

L2-06

0.0 s

Sets the deceleration time during KEB.

KEB Acceleration
Time After Power
Recovery

L2-07

0.0 s

L2-07

0.0 s

Momentary Power
Loss Process

Frequency Gain at
KEB Start

L2-08

100 %

L2-08

100 %

Parameter Name

F7

A1000

Setting

Parameter

Default

Parameter

Default

F7

A1000