10 Appendix 2 Parameter Cross Reference

YASKAWA PL.A1000.02 F7 to A1000 - Product Transition Guide

47

Analog Input

Terminal A1
Signal Level
Selection

H3-01

0

H3-01

0

Terminal A1 in A1000 is multi-functional.

H3-01

H3-01

0: 0 to +10 V

0: 0 to +10 V (uses lower limit)

1: -10 to 10 V

1: -10 to 10 V (no lower limit)

Terminal A1
Function Selection

H3-02

0

For A1000, set H3-02 to 0.

Terminal A1 Gain
Setting

H3-02

100.0%

H3-03

100.0 %

F2-02

100.0 %

Set this parameter when using an analog option card to determine the gain added to
the analog reference.

Terminal A1 Bias
Setting

H3-03

0.0%

H3-04

0.0 %

F2-03

0.0 %

Set this parameter when using an analog option card to determine the gain added to
the analog reference.

Terminal A3
Signal Level
Selection

H3-04

0

H3-05

0

H3-04

H3-05

0: 0 to +10 V

0: 0 to +10 V (uses lower limit)

1: -10 to 10 V

1: -10 to 10 V (no lower limit)

Terminal A3
Function Selection

H3-05

2

H3-06

2

H3-05, H3-09

H3-06, H3-10

0: Terminal A1 bias

0: Frequency bias

1: Frequency reference
gain

1: Frequency gain

2: Auxiliary freq ref 1

2: Auxiliary freq ref 1

3: Auxiliary freq ref 2

3: Auxiliary frequency reference 2

4: Output voltage bias

4: Output voltage bias

5: Accel/decel time
coefficient

5: Accel/decel time gain

6: DC Injection Braking
current

6: DC Injection Braking current

7: Torque detection level

7: Torque detection level

8: Stall Prevention level
during run

8: Stall Prevention level during run

9: Frequency Ref. lower
limit

9: Output freq lower limit level

A: Jump frequency 4

B: PID feedback

B: PID feedback

C: PID setpoint

C: PID setpoint

D: Frequency Reference
bias 2

D: Frequency bias

E: Motor temperature

E: Motor temperature

F: Through- mode

F: Through- mode

Parameter Name

F7

A1000

Setting

Parameter

Default

Parameter

Default

F7

A1000