Product Transition Guide
GPD506/P5 to F7

PL.F7.05 Page

16

of 54

GPD506/P5 Terminal

F7 Terminal

(Designations similar to GPD506/P5)

Type

GPD506/P5

Terminal

Default Function & Description

F7

Terminal

Default Function

F7 Description

FS

+15V Power supply output for
analog command
(Allowable current, 20mA max.)

+V

+15Vdc power output

+15Vdc
(Max. current: 20mA)

-V

-15Vdc power output

-15Vdc
(Max. current: 20mA)

FV

Frequency reference input
(voltage) 0 to +10V/100%,
n043 = “FV=MSTR”:
FV enabled
n043 = “FI=MSTR”:
FI enabled
0 to +10V (20kW)

A1

Analog input or speed
command

0 to +10Vdc=100%
0 to +/-10Vdc =100%
(H3-01) (20k ohm)

FI

Frequency reference input
(current) 4 to 20mA/100%
n043 = “FV=MSTR”:
FV enabled
n043 = “FI=MSTR”:
FI enabled
4 to 20mA (250W)

A2

Add to terminal A1

4 to 20mA=100%/(250 ohms)
0 to +10Vdc=100%/(20k ohm)
Function set by H3-09.

A3

Aux. frequency reference 1

0 to +10Vdc=100%/(20k ohm)
0 to +/-10Vdc=100%
Function set by H3-05

FC

Common terminal 0V

AC

Analog common

Anal

og Input

Si

gnal

s

E(G)

Connection to shield sheath of
signal lead

E(G)

Shield wire, optional ground
line connection point

M1 M1

M2

During running (N.O. contact)
Closed when running.
Multi-function contact output
(n042)
Dry contact capacity:
250VAC 1A or less
30VDC 1A or less

M2

During run
(N.O. contact)

Form A Dry contacts capacity:
1 A max. at 250Vac
1 A max. at 30Vdc
Multi-function digital output.
Function set by H2-01.

M3

M4

Zero speed
(N.O. contact)

Form A Dry contacts capacity:
1 A max. at 250Vac
1 A max. at 30Vdc
Multi-function digital output.
Function set by H2-02.

M5

M6

Frequency agree
(N.O. contact)

Multi-function digital output.
Function set by H2-03.







MA MA

Dig

ital Ou

tp

ut

Sig

na

ls

MB

Fault contact output
(N.O./N.C. contact)

MB

Fault output signal
(SPDT)

Form C Dry contacts
capacity:

Advertising