GPD506/P5 to F7

PL.F7.05 Page

8

of 54

GPD506/P5 to F7 Specification Differences (continued)

Feature

or Function

Item

Yaskawa GPD506/P5

Yaskawa F7

Design Features (continued)

Standard

Modbus RTU via RS232

Modbus RTU via built in

RS485/422

Network Communications

Optional

RS232 to RS485, DeviceNet,

Lonworks, ApogeeFLN,

MetasysN2

DeviceNet, Profibus-DP,

Interbus-S, CAN Open, CC- Link,

Ethernet

Diagnostics

Fault Storage

Last 4 Faults

Last 10 Faults with Elapsed Time,

Most Recent Fault with all

Operating Conditions

Quick Disconnect I/O
Terminals Type

No

Yes (Phoenix)

With split front cover for easy

wiring

Auto-Tuning

Rotating/Stationary

No

Rotating (dynamic)

Stationary (static)

Primary Resistance

Bi/Uni-Directional Uni-Directional Bi-Directional

Speed Search
Synchronized Start

Method Current

Current/Speed

Analog Input Signal

Filter

No Yes

PI / PID Control

Two Feedback

No

Yes

Sleep Function

In Open Loop Mode

No

Yes

Automatic Restart

Time Between

Attempts

Not Adjustable

0.0 – 5.0 sec (selectable)

V/Hz Patterns

Qty.

1 Preset, 1 Custom

15 Preset, 1 Custom

Skip Frequencies

Qty.

2

3

Preset Speeds

Qty.

6

17

Custom Drive Software

Embedded

No

CASE w/flash memory

Parameter Upload/Download

PC Software

InverterWin

Drive Wizard Software

Accel/Decel Time

Sec.

0.0 - 3600.0 sec

0.1 - 6000.0 sec.

Analog Input Filter

No

Yes

Closed Loop PID Control

Two Feedback

No

Yes

Sleep Function

In Open Loop Mode

No

Yes

DC Injection Function

At Start/At Stop

At Start/At Stop

At Start/At Stop (adjustable)

+HSB during stop

DB Transistor

Built-in to 10HP (VT-230V)
Built-in to 25HP (VT-460V)

Built-in to 25HP

Braking Function

Special No

High Slip Braking all models

(Faster stopping without options)

On/Off Control

Power-up based

Run Based

Service Disassembly

required

Modular/pluggable fan select

models

Cooling Fan

Operating Hours

Drive power-up hours logged

Logged

Timer Function

On/Off Delay

On/Off Delay (0-25.5 sec)

On Delay at start (0-600 sec)

On/Off Delay Timer ( 0-3000sec)

Advertising