Nec hp ratings for 460v normal duty models – Yaskawa GPD 506/P5 to F7 User Manual

Page 28

Advertising
background image

Product Transition Guide
Appendix 1 –Ratings and Heat Loss Comparison

PL.F7.05 Page

28

of 54

NEC HP Ratings for 460V Normal Duty Models

GPD506/P5 460V Models

F7 480V Models

Variable Torque

(n116=1)

Normal

Duty

(C6-02=2)

NEC

HP

460V

NEC

Amps

GPD506/P5

Model

CIMR-P5U

Output

Amps

Fc kHz

OL %

VT

1 minute

F7

Model

CIMR-F7U

Output

Amps

Fc

kHz

Overload %

ND

1 minute

0.5 1.1 40P41 1.9 10 120

0.75 1.6

40P41 1.8 15 120

1 2.1 40P71 3.6 10 120

40P71 2.1 15 120

1.5 3

2 3.4

41P51 3.7 15 120

3 4.8 41P51 5.1 10 120

42P21 6.6 10 120

42P21 5.3 15 120

5.0 7.6 43P71 8.5 10 120

43P71 7.6 15 120

44P01 8.7 15 120

7.5 11 44P01 11.7 10 120

45P51 12.5 15 120

10 14 45P51 14.8 10 120

47P51 17 15 120

15 21 47P51 21 10 120

20 27 40111 28.6 10 120

40111 27 8 107

25 34 40151 34 10 120

40151 34 10 109

30 40 40181 41 10 120

40181 40 10 117

40 52 40221 52 8 120

50 65 40301 65 5 120

40301 67.2 8

107

60 77 40371 80 5 120

40371 77 8 117

75 96 40451 96 5 120

40451 96 8 114

100 124 40551 128 5 120

40551 125 5

108

125 156 40751 180 5 120

40751 156 5

115

150 180

40901 180 8

120

200 240 41101 240 5 120

41101 240 5

108

41321 260 5

120

250 302 41601 302 5 120

41601 304 5

120

300 361 41850 380 2.5 120

350 414 42200 506 2.5 120

41850 414 2

107

400 477

450 506

42200 506 2

118

500 590 43000 675 2.5 120

550 660

43000 675 2

120


Advertising