Appendix 3- Parameter Cross Reference

PL.F7.05 Page

46

of 54

GPD506/P5 Parameter

F7 Parameter

Param

No.

Nxxx

Parameter

Name

Description or Selection

Description or Selection

Parameter

Name

Param.

No.

048

Terminal FV gain

Set unit: 1% and set range: 0 to 200%

0.0 to1000.0
Sets the output level when 10V is input, as
a percentage of the maximum output
frequency (E1-04).

Terminal A1 Gain Setting

H3-02

049

Terminal FV bias

Set unit: 1% and set range = -100 to +100%

–100.0 to +100.0
Sets the output level when 0V is input, as a
percentage of the maximum output
frequency (E1-04).

Terminal A1 Bias Setting

H3-03

050

Terminal FI gain

Set unit: 1% and set range: 0 to 200%

0.0 to 1000.0
Sets the output level when 10V is input.

Terminal A2 Gain Setting

H3-10

051

Terminal FI bias

Set unit: 1% and set range -100 to +100%

–100.0 to+100.0
Sets the output level when 0V is input.

Terminal A2 Bias Setting

H3-11

052

Analog output
Select
(terminal AM-AC)

0: Output frequency
(10V = Max frequency n011)
1: Output current
(10V = rated current of inverter)
2: Output power (10V = inverter rated power)
3: DC bus voltage (10V = 1150VDC)

Selects which monitor will be output on
terminals FM and FC.
1: Frequency Reference
100% = Maximum output frequency
2: Output Frequency
100% = Maximum output frequency
3: Output Current
100% = Drive rated current.
5: Motor Speed
100% = Maximum output frequency
6: Output Voltage
100% = 200/400Vac depending on Drive
voltage rating.
7: DC Bus Voltage
100% = 400/800Vdc depending on Drive
voltage rating.
8: Output kWatts
100% = Drive rated power.
9: Torque Reference
100% = Motor rated torque.
15: Terminal A1 Input Level
100% = 10Vdc
16: Terminal A2 Input Level
100% = 10Vdc or 20mA
17: Terminal A3 Input Level
100% = 10Vdc
18: Motor Secondary Current
100% = Motor rated secondary current.
19: Motor Excitation Current
100% = Motor rated secondary current.
20: SFS Output
100% = Maximum output frequency
21: ASR Input
100% = Maximum output frequency
22: ASR Output
100% = Maximum output frequency
24: PID Feedback
100% = Maximum output frequency.
26:Output Voltage Reference Vq
100% = E1-05, default 240V or 480V.
27: Output Voltage Reference Vd
100% = E1-05, default 240V or 480V.
31: Not Used
36: PID Input
100% = Maximum output frequency
37: PID Output
100% = Maximum output frequency
38: PID Setpoint
100% = Maximum output frequency
45: Feedforward Control Output
100% = Motor rated secondary current.

Terminal FM Monitor
Selection

H4-01

053

Analog output gain

Set unit: 0.01 and set range: 0.01-2.00

0.0 to 1000.0
Sets terminal FM output level when
selected monitor is at 100%.

Terminal FM Gain Setting

H4-02