Appendix 3- parameter cross reference, Parameter name – Yaskawa GPD 506/P5 to F7 User Manual

Page 44

Advertising
background image

Appendix 3- Parameter Cross Reference

PL.F7.05 Page

44

of 54

GPD506/P5 Parameter

F7 Parameter

Param

No.

Nxxx

Parameter

Name

Description or Selection

Description or Selection

Parameter

Name

Param.

No.

(con’t)

041















































(con’t)

Multi-function
contact output 1
(terminal MA-MB-MC)





































































Multi-function

12: Timer Output
Output for independent timer,
controlled by b4-01 and b4-02. Used in
conjunction with the digital input
H1-

= 18 “timer function”.

13: Fref/Fout Agree 2
Closed = When Drive output frequency
equals the frequency reference +/- the
hysteresis of L4-04.
14: Fref/Set Agree 2
Closed = When the Drive output
frequency and the frequency reference
are equal to the value in L4-03 +/- the
hysteresis of L4-04.
15: Frequency Detection 3
Closed = When the Drive output
frequency is less than or equal to the
value in L4-03 with the hysteresis
determined by L4-04.
16: Frequency Detection 4
Closed = When the Drive output speed
is greater than or equal to the value in
L4-03, with the hysteresis determined
by L4-04.
17: Torque Detection 1 N.C.
Open = When the output current/torque
exceeds the value set in parameter
L6-02 for more time than is set in
parameter L6-03.
18: Torque Detection 2 N.O.
Closed = When the output
current/torque exceeds the value set in
parameter L6-05 for more time than is
set in parameter L6-06.
19: Torque Detection 2 N.C.
Open = when the output current/torque
exceeds the value set in parameter
L6-05 for more time than is set in
parameter L6-06.
1A: Reverse Direction
Closed = When the Drive is running in
the reverse direction.
1B: Baseblock 2 N.C.
Open = When Drive is not outputting
voltage.
1C: Motor 2 Selection
Closed = When motor 2 is selected by
multi-function input “motor 2
selection”.
1D: Regenerating
Closed = When in regenerating mode.
1E: Restart Enabled
Closed = When the Drive is performing
an automatic restart attempt. Automatic
restart is configured by parameter
L5-01.
1F: Overload (OL1)
Closed = When OL1 function is at 90%
of its trip point or greater.
20: OH Alarm
Closed = When the Drive’s heatsink
temperature exceeds the setting of
parameter L8-02.
30: During Torque Limit
(when in speed control)
Closed = When in torque limit.
31: During Speed Limit
Closed = When in speed limit.




32: During Speed Limit

Terminal M1-M2 Function
Selection






































































H2-01